ELE04-00421
| Temporary Service | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
###-#### larry 110.12(A) unused openings shall be closed, 110.3, Fittings shall be listed for the purpose, 404.7 Breaker handle in up position shall be on not off. 2/2/2005 10:11:47 AM
|
ELE04-03856
| Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | CANC |
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Jan Rice contr called and cancelled until tomorrow 2/2/2005 8:38:05 AM
|
ELE04-03617
| Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final 2/2/2005 8:27:50 AM
|
ELE04-03618
| Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice 314.43 screws shall not be in plastic box, 314.25 boxes shall have covers installed 2/2/2005 8:30:33 AM
|
ELE05-00187
| Electrical Rough-In | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | CANC |
|
|
Jennifer; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
ELE05-00020
| Final | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/2/2005 at 6:55:58 AM. Contact: ###-####. called contr. to change a/c breaker from 30 to 25A. 2/2/2005 9:02:01 AM
|
ELE05-00296
| Rough-In Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn ric ok p/s u/g n ok 2/2/2005 10:30:54 AM
|
ELE03-03302
| Final | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice told owner to rewire outside gfci, and space 1 recpt for depth, also to change fixture at bathtub to damp location fixture. ok to final. 2/2/2005 12:27:20 PM
|
ELE05-00336
| Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Please call Bob Kiah prior to heading out so he can meet you to unlock the house ###-####..; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen Called contr to gain entry, he sent realtor out. The following need fixed as a minimum. 110.12(A) unused opening in bottom of meter needs closed. Ground wire entering 1" threaded opening. 440.22(C) a/c fuses shall not exceed mfgr's value, 250.56 single electrode shall be supplemented by additional one ,200.7 white wire for grounded ckt only, 310.16 max ampacity #14 wire to be 15A, 250.86 raceway shall be grounded thru concentric,334.30 nm cable shall be protected for washer and dryer, 334.30(A) metal conduit shall be strapped within 3' of meter,250.104 metal water piping shall be bonded, 408.4 panel shall have directory, 200.6(B) neutral shall be identified, BCC shall post job sticker. 2/2/2005 4:31:37 PM
|
ELE04-04000
| Final | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
better homes; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Can't final without a/c unit, GFCI in bathroom and by front door don't work. 210.8(A) Called contr. and left correction notice 2/2/2005 1:38:29 PM
|
ELE05-00187
| Electrical Rough-In | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
Jennifer; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made ric ok 2/2/2005 1:58:03 PM
|
ELE04-03385
| Final | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | NH |
|
|
Please call for access codes jay; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, no answer, left message to get code. 2/2/2005 1:49:35 PM
|
ELE04-03386
| Final | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | NH |
|
|
call for acces code jay; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, couldn't get access code because he didn't answer. Left message. 2/2/2005 2:17:07 PM
|