FIR04-00635
| FIR-Aging Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | | PART |
|
|
In progress 2/2/2005 7:55:16 AM
|
FIR04-00609
| INSP-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
|
BLD03-00726
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
Per plans - need extinguishers; north and south door hardware; exit sign shown on plans? 2/2/2005 10:31:43 AM
|
FIR04-00161
| INSP-Sprinkler Rough-in/Hydro | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PART |
|
|
Air test okay; need to add EQ at new main; different heads used in underfloor area; need as-builts for addition to under floor in phone room 2/2/2005 9:45:34 AM
|
BLD02-00266
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
|
BLD02-00266
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | PASS |
|
|
Final okay 2/2/2005 10:49:18 AM
|
FIR05-00031
| INSP-Final Inspection | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
ronny; Phone #: ###-#### Internet Inspection Request from: Barbara Moore East riser hydro okay; west riser has minor leak at vic at top of riser - will need to do hydro test over; sprinkler and anti=freeze loop overdue annual certification 2/2/2005 10:48:14 AM
|
MIS05-00016
| FIR-Final | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
tim bergey --###-#### --pending bld fn
|
BLD04-00360
| FIRE-Final Inspection | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
marty; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Final okay 2/2/2005 2:09:00 PM
|
FIR04-00358
| INSP-Sprinkler Rough-in | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PART |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 2nd and 3rd floors hydro and r/i's all complete 2/2/2005 1:51:23 PM
|
FIR04-00149
| INSP-Final Inspection | 1/28/2005 | 2/2/2005 | 2/1/2005 12:32:34 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 1/28/2005 at 10:58:06 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 1 2005 12:32PM.
|