Inspections for the day of: Wednesday, February 2, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00635 FIR-Aging Inspection2/2/20052/2/20052/2/2005 12:00:00 AM PART
In progress 2/2/2005 7:55:16 AM
FIR04-00609 INSP-Final Inspection2/2/20052/2/20052/2/2005 12:00:00 AMAPASS
BLD03-00726 FIRE-Final Inspection2/2/20052/2/20052/2/2005 12:00:00 AMAFAIL
Per plans - need extinguishers; north and south door hardware; exit sign shown on plans? 2/2/2005 10:31:43 AM
FIR04-00161 INSP-Sprinkler Rough-in/Hydro2/2/20052/2/20052/2/2005 12:00:00 AMAPART
Air test okay; need to add EQ at new main; different heads used in underfloor area; need as-builts for addition to under floor in phone room 2/2/2005 9:45:34 AM
BLD02-00266 FIRE-Final Inspection2/2/20052/2/20052/2/2005 12:00:00 AMAPASS
BLD02-00266 FIRE-Final Inspection2/2/20052/2/20052/2/2005 12:00:00 AMAPASS
Final okay 2/2/2005 10:49:18 AM
FIR05-00031 INSP-Final Inspection2/1/20052/2/20052/2/2005 12:00:00 AMAFAIL
ronny; Phone #: ###-#### Internet Inspection Request from: Barbara Moore East riser hydro okay; west riser has minor leak at vic at top of riser - will need to do hydro test over; sprinkler and anti=freeze loop overdue annual certification 2/2/2005 10:48:14 AM
MIS05-00016 FIR-Final2/1/20052/2/20052/2/2005 12:00:00 AMPPASS
tim bergey --###-#### --pending bld fn
BLD04-00360 FIRE-Final Inspection2/1/20052/2/20052/2/2005 12:00:00 AMPPASS
marty; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Final okay 2/2/2005 2:09:00 PM
FIR04-00358 INSP-Sprinkler Rough-in2/1/20052/2/20052/2/2005 12:00:00 AMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 2nd and 3rd floors hydro and r/i's all complete 2/2/2005 1:51:23 PM
FIR04-00149 INSP-Final Inspection1/28/20052/2/20052/1/2005 12:32:34 PMACANC
Scheduled by a contractor via Hello! on 1/28/2005 at 10:58:06 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 1 2005 12:32PM.