FIR03-00440
| INSP-Conference | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | DONE |
|
|
I spoke to Don with Superior Fire and he said he would be willing to take over this job and would get the inspection called in. 2/2/2005 10:21:46 AM
|
BLD04-02158
| FIRE-Sprinkler Rough-in | 2/1/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | A | FAIL |
|
|
Dusty; Phone #: ###-#### Riser is exposed cpvc piping. Meet review note #31 or change to steel piping. Plans show dry sidewall heads in the garage. Standard sidewall heads have been installed. Provide the additional tenting and insulation as discussed. Overhead piping on plans is shown as 1". But 1 1/4" piping has been installed . See plans for location. Finish framing the pantry. Resubmitt plans showing the changes or make modifications before ok to cover. 2/2/2005 9:26:57 AM
|
BLD04-01740
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | PASS |
|
|
Life safety finaled 2/2/2005 1:31:33 PM
|
FIR04-00754
| INSP-Alarm Testing | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Trouble does not report on the duct detectors. 2/2/2005 3:46:35 PM
|
BLD04-00888
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Final fhe fire alarm permit 2/2/2005 3:46:58 PM
|
BLD03-02995
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|
BLD03-02995
| FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 12:00:00 AM | P | FAIL |
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|