Inspections for the day of: Thursday, February 2, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00578 INSP-Final Inspection1/31/20062/2/20062/3/2006 12:47:44 PMPFAIL
The WON door on the 10th floor failed to function properly, batteries for the transponder panel for the 8th floor failed, one a/v in the short hall on 6th floor failed to operate, a/v devices at the restroom vestibules and select elevator lobbies have been relocated from location shown on approved plans (shown on as builts), one a/v on the 8th floor has been deleted in a vestibule that does not exist. Floors 5-11 core and common areas tested at this time.
BLD05-02851 FIRE-Final Inspection1/25/20062/2/20062/2/2006 2:32:15 PMPPASS
Fire life safety is complete, inspection passed.
FIR05-00692 INSP-Final Inspection1/25/20062/2/20062/2/2006 2:30:58 PMPPASS
Fire sprinkler related to this scope of work is acceptable. The overspaced existing heads adjacent to this area are noted on plans to be corrected under a future permit.
FIR05-00691 INSP-Final Inspection1/25/20062/2/20062/2/2006 2:26:15 PMPPASS
Fire alarm work is satisfactory, inspection passed.
BLD05-02737 FIRE-Final Inspection1/25/20062/2/20062/2/2006 2:24:44 PMPPART
Life safety is satisfactory, final pending related alarm permit corrections.
FIR05-00650 INSP-Final Inspection1/25/20062/2/20062/2/2006 2:23:03 PMPPASS
Fire sprinkler work is satisfactory, inspection passed.
FIR05-00649 INSP-Final Inspection1/25/20062/2/20062/2/2006 2:22:11 PMPFAIL
One 30cd strobe is installed below the min. allowed height per NFPA 72, strobes are not in synchronization as required.
FIR05-00844 INSP-Final Inspection1/25/20062/2/20062/2/2006 2:01:33 PMPFAIL
Heat collector has been provided on one head (provide listing), one sprinkler head exceeds 22" from the deck, sprinkler heads may be required in each beam pocket, sprinkler piping installed is 1 1/2 plans show 2".
BLD05-03099 FIRE-Conference2/1/20062/2/20062/2/2006 11:01:45 AMADONE
matt; Phone #: ###-#### Conference to discuss related permit requirements and basic life safety items for this TI.
FIR06-00059 INSP-Sprinkler Rough-in/Hydro2/1/20062/2/20062/2/2006 10:49:52 AMAPART
Overhead fire sprinkler work is satisfactory, will final permit when ceiling tile and escutcheons are installed.