FIR05-00578
| INSP-Final Inspection | 1/31/2006 | 2/2/2006 | 2/3/2006 12:47:44 PM | P | FAIL |
|
|
The WON door on the 10th floor failed to function properly, batteries for the transponder panel for the 8th floor failed, one a/v in the short hall on 6th floor failed to operate, a/v devices at the restroom vestibules and select elevator lobbies have been relocated from location shown on approved plans (shown on as builts), one a/v on the 8th floor has been deleted in a vestibule that does not exist. Floors 5-11 core and common areas tested at this time.
|
BLD05-02851
| FIRE-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:32:15 PM | P | PASS |
|
|
Fire life safety is complete, inspection passed.
|
FIR05-00692
| INSP-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:30:58 PM | P | PASS |
|
|
Fire sprinkler related to this scope of work is acceptable. The overspaced existing heads adjacent to this area are noted on plans to be corrected under a future permit.
|
FIR05-00691
| INSP-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:26:15 PM | P | PASS |
|
|
Fire alarm work is satisfactory, inspection passed.
|
BLD05-02737
| FIRE-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:24:44 PM | P | PART |
|
|
Life safety is satisfactory, final pending related alarm permit corrections.
|
FIR05-00650
| INSP-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:23:03 PM | P | PASS |
|
|
Fire sprinkler work is satisfactory, inspection passed.
|
FIR05-00649
| INSP-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:22:11 PM | P | FAIL |
|
|
One 30cd strobe is installed below the min. allowed height per NFPA 72, strobes are not in synchronization as required.
|
FIR05-00844
| INSP-Final Inspection | 1/25/2006 | 2/2/2006 | 2/2/2006 2:01:33 PM | P | FAIL |
|
|
Heat collector has been provided on one head (provide listing), one sprinkler head exceeds 22" from the deck, sprinkler heads may be required in each beam pocket, sprinkler piping installed is 1 1/2 plans show 2".
|
BLD05-03099
| FIRE-Conference | 2/1/2006 | 2/2/2006 | 2/2/2006 11:01:45 AM | A | DONE |
|
|
matt; Phone #: ###-#### Conference to discuss related permit requirements and basic life safety items for this TI.
|
FIR06-00059
| INSP-Sprinkler Rough-in/Hydro | 2/1/2006 | 2/2/2006 | 2/2/2006 10:49:52 AM | A | PART |
|
|
Overhead fire sprinkler work is satisfactory, will final permit when ceiling tile and escutcheons are installed.
|