FIR08-00716
| FIR-Aging Inspection | 2/2/2009 | 2/2/2009 | 2/5/2009 3:46:21 PM | | DONE |
|
|
Work is in progress.
|
BLD08-02580
| FIRE-Final Inspection | 2/2/2009 | 2/2/2009 | 2/2/2009 4:04:34 PM | P | PASS |
|
|
Life safety passed.
|
BLD08-01652
| FIRE-Final Inspection | 1/30/2009 | 2/2/2009 | 2/2/2009 3:02:11 PM | A | PASS |
|
|
Life safety passed. The storage racks that exceed 8'-0" in height have been removed as well as the aerosols and solvents.
|
FIR08-00636
| INSP-Alarm Testing | 1/30/2009 | 2/2/2009 | 2/2/2009 2:57:56 PM | A | PASS |
|
|
Permit finaled. Storage was below 20'-0" at this time. Owner has been notified by the sprinkler contractor that 18" minimum clearance is required from the top of the storage to the sprinkler heads.
|
BLD07-01278
| FIRE-Final Inspection | 1/30/2009 | 2/2/2009 | 2/2/2009 2:55:03 PM | A | PASS |
|
|
Life safety passed.
|
FIR08-00772
| INSP-Final Inspection | 1/29/2009 | 2/2/2009 | 2/2/2009 2:53:48 PM | A | FAIL |
|
|
Provide hydro testing per NFPA 13 and 25. Provide data sheets for the newly installed valve on the backflow preventor. Provide as-builts.
|
BLD06-02722
| FIRE-Final Inspection | 1/30/2009 | 2/2/2009 | 2/2/2009 11:52:30 AM | A | PASS |
|
|
Life safety passed.
|
BLD08-02541
| FIRE-Final Inspection | 1/30/2009 | 2/2/2009 | 2/2/2009 10:33:53 AM | A | PASS |
|
|
Life safety passed
|