ELE16-04017
| Electrical Rough-In | 2/1/2017 | 2/2/2017 | 2/3/2017 2:15:42 PM | P | NR |
|
|
Underground. at 3pm if possible please. George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Underground did not get installed will recall when ready
|
ELE17-00249
| Temporary Service | 2/1/2017 | 2/2/2017 | 2/2/2017 11:01:25 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Temp pole not set. Drove by missing pole on lot.
|
ELE17-00248
| Temporary Service | 2/1/2017 | 2/2/2017 | 2/2/2017 11:00:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE17-00247
| Temporary Service | 2/1/2017 | 2/2/2017 | 2/2/2017 10:05:11 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Pole not set yet. Called and informed missing.
|
ELE17-00250
| Temporary Service | 2/1/2017 | 2/2/2017 | 2/2/2017 10:04:00 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Duplicate permit. Temp pole approved on permit ELE16-03853 in November. Drove to lot and found meter installed and energized.
|
ELE17-00037
| Conference | 2/1/2017 | 2/2/2017 | 2/2/2017 8:52:49 AM | A | DONE |
|
|
Consultation for Building #1 Contact Cesar Salcedo. Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek Contractor wanted to check for approval on receptacle outlets each side of bed. The units are guest rooms. As per 210.60(B)- receptacles shall be located so attachment plug will not be in contact with bed furniture. They will install a junction box behind removeable headboard and move receptacle where needed.
|