Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04017 Electrical Rough-In2/1/20172/2/20172/3/2017 2:15:42 PMPNR
Underground. at 3pm if possible please. George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Underground did not get installed will recall when ready
ELE17-00249 Temporary Service2/1/20172/2/20172/2/2017 11:01:25 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Temp pole not set. Drove by missing pole on lot.
ELE17-00248 Temporary Service2/1/20172/2/20172/2/2017 11:00:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
t/s u/g n ok
ELE17-00247 Temporary Service2/1/20172/2/20172/2/2017 10:05:11 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Pole not set yet. Called and informed missing.
ELE17-00250 Temporary Service2/1/20172/2/20172/2/2017 10:04:00 AMACANC
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Duplicate permit. Temp pole approved on permit ELE16-03853 in November. Drove to lot and found meter installed and energized.
ELE17-00037 Conference2/1/20172/2/20172/2/2017 8:52:49 AMADONE
Consultation for Building #1
Contact Cesar Salcedo.
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Contractor wanted to check for approval on receptacle outlets each side of bed. The units are guest rooms.
As per 210.60(B)- receptacles shall be located so attachment plug will not be in contact with bed furniture. They will install a junction box behind removeable headboard and move receptacle where needed.