FIR02-00437
| FIR-Aging Inspection | 2/20/2003 | 2/20/2003 | 2/20/2003 12:00:00 AM | | PART |
|
|
e-mailed Dan B to forward message to responsible party that I need a status of this project 2/20/2003 10:47:07 AM
|
FIR02-00338
| INSP-Sprinkler Rough-in | 2/19/2003 | 2/20/2003 | 2/20/2003 12:00:00 AM | A | PASS |
|
|
43 psi air test okay on dry air test 2/20/2003 9:39:42 AM
|
BLD00-03428
| FIRE-Sprinkler Rough-in | 2/19/2003 | 2/20/2003 | 2/20/2003 12:00:00 AM | A | FAIL |
|
|
calvin; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie not a sprinkler r/i' checked smoke/fire damper operation - basement dampers are all okay now; started checking other floors; first floor ceiling detectors at vestibules are sampling tube type on 2 west vestibules and should be in-duct detectors as the sampling tubes won't work properly due to location; several dampers on first and second floor not working and will need to verify operaration 2/21/2003 9:20:21 AM
|
BLD00-02893
| FIRE-Final Inspection | 2/20/2003 | 2/20/2003 | 2/20/2003 12:00:00 AM | P | FAIL |
|
|
talked to Tom A. and we will need plans; called and talked to the manager and told her that we will need approved plans; she was going to call the corporate office and let them know 2/21/2003 9:28:50 AM
|