Inspections for the day of: Friday, February 20, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00458 Electrical Rough-In2/19/20042/20/20042/20/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/19/2004 at 11:55:49 AM. Contact: ###-####. cor. posted called 300.4(D) 11/4" for MC and flex all 8 units 2/20/2004 9:15:31 AM
ELE04-00391 Final2/19/20042/20/20042/20/2004 12:00:00 AMAPASS
###-#### Saysaymone permanent occupancy ok 2/20/2004 10:01:39 AM
ELE03-00940 Final2/19/20042/20/20042/20/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/19/2004 at 1:36:16 PM. Contact: ###-####. ok 2/20/2004 8:31:51 AM
ELE04-00183 Electrical Rough-In2/19/20042/20/20042/20/2004 12:00:00 AMAPASS
Scott; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 2/20/2004 11:06:11 AM
ELE03-03974 Final2/19/20042/20/20042/20/2004 12:00:00 AMPPASS
mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 14 ok no card at house 2/20/2004 2:57:57 PM
ELE03-03905 Electrical Rough-In2/19/20042/20/20042/20/2004 12:00:00 AMPNR
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes walls east end 2nd floor 2/20/2004 12:38:08 PM
ELE04-00214 Final2/20/20042/20/20042/20/2004 12:00:00 AMPFAIL
Please call above number for access. Electrical concerns on project should be directed to ###-####.; Phone #: ###-#### Internet Inspection Request from: Dawn Moore cor. posted met with contractor 410.8 needs shelves installed in MB closets 110.3(B) provide instructions or gfci for fan above tub, shower in bathrm, provide access to recept for jtub so it can be tested and serviced 2/20/2004 2:04:41 PM
ELE04-00367 Electrical Rough-In2/20/20042/20/20042/20/2004 12:00:00 AMPNR
duncan- ###-#### r/i for kit NR conference ok 2/20/2004 3:59:42 PM
ELE04-00401 Electrical Rough-In2/20/20042/20/20042/20/2004 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Andy Rose r/i ok correction for p/s 2/20/2004 1:25:43 PM
ELE04-00327 Rough-In Permanent Service2/19/20042/20/20042/20/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/19/2004 at 2:15:34 PM. Contact: ###-####. Scott will call for final
p/s u/g new for meter in electrical rm ok 2/20/2004 3:27:03 PM