Inspections for the day of: Friday, February 20, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00064 FIRE-Final Inspection2/19/20042/20/20042/20/2004 12:00:00 AMAFAIL
Repair exit sign at the main exit. Provide approved door hardware on the south facing door in office. Remove thumb turn on the main exit. 2/20/2004 10:42:34 AM
BLD03-00602 FIRE-Sprinkler Rough-in2/19/20042/20/20042/20/2004 12:00:00 AMANR
Inspection was for installation of the fire dampers on the third floor. As of 11:20 am only three had been installed. 2/20/2004 11:17:28 AM
BLD03-00602 FIRE-Sprinkler Rough-in2/19/20042/20/20042/20/2004 12:00:00 AMACANC
chuck; Phone #: ###-#### Internet Inspection Request from: Annette Moore
MIS04-00052 FIR-Final2/18/20042/20/20042/20/2004 12:00:00 AMAFAIL
Repair the exit sign/emergency light at 254 suite entrance. Remove deadbolt from 252 suite entrance. Remove thumbturn from backdoor to suite 258 and provide lever hardware per review note on plans 2/20/2004 9:42:26 AM
BLD03-03051 FIRE-Final Inspection2/19/20042/20/20042/20/2004 12:00:00 AMAFAIL
Provide fire extinguisher per review note #8 and provide verification of review note #13 2/20/2004 8:54:33 AM
FIR04-00048 INSP-Sprinkler Rough-in/Hydro2/19/20042/20/20042/20/2004 12:00:00 AMPPART
hydro test is ok 2/20/2004 4:04:21 PM
BLD03-00602 FIRE-Conference2/20/20042/20/20042/20/2004 12:00:00 AMPPART
I inspected the east wing fire damper. Installation appears to be OK. Asked the installing contractor to provide additional fire caulking between damper and housing 2/20/2004 3:11:00 PM
FIR03-00594 INSP-Sprinkler Rough-in/Hydro2/20/20042/20/20042/20/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/20/2004 at 8:58:08 AM. Contact: ###-####.
BLD04-00064 FIRE-Final Inspection2/20/20042/20/20042/20/2004 12:00:00 AMPPASS
fire life safety finaled 2/20/2004 3:26:30 PM
BLD03-01348 FIRE-Final Inspection2/20/20042/20/20042/20/2004 12:00:00 AMPFAIL
Provide annual inspection tag for existing fire extinguisher. Provide one more fire extinguisher. Remove thumbturn from office door. Provide lever hardware for office door.