Inspections for the day of: Tuesday, February 20, 2007.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00125 INSP-Final Inspection2/19/20072/20/20072/21/2007 2:52:17 PMAFAIL
Booth suppression system activated when the test link was cut. The air supply for painting shut off as well. The booth does not have the 3' clearance as required but seems to meet the exception for being against a non combustible wall. The wall is cinderblock which supports a sheetrock ceiling. The item that is a problem is the heater for the curing/baking process is direct fire which is not allowed per code. Also the distance from property lines and openings needs verified as well as the height of the exhaust discharge piping. Matt was going to have his booth supplier contact sam rogers about their booth and its operation. Also I had matt program in the required 3 minute delay before the heater comes on per code and per matt the unit has a high limit switch set at 200 degrees. The fire extinguisher is also ok.
FIR07-00098 INSP-Final Inspection2/20/20072/20/20072/21/2007 12:53:52 PMPFAIL
Sound levels were not adequate in the sleeping areas.
FIR07-00101 INSP-Final Inspection2/16/20072/20/20072/21/2007 10:10:10 AMPFAIL
A standard coverage pendant, next to the windows has been installed where an extended coverage head should have been installed. This heads spacing has been exceeded.
FIR06-00880 INSP-Final Inspection2/20/20072/20/20072/21/2007 9:44:24 AMPFAIL
Need to flush the underground and relocate the outside alarm bell to the FDC location
BLD06-03118 FIRE-Final Inspection2/20/20072/20/20072/21/2007 8:35:36 AMPCANC
No time for inspection. To be rescheduled for tomorrow
FIR06-00755 INSP-Sprinkler Rough-in/Hydro2/19/20072/20/20072/21/2007 7:58:29 AMACANC
There is no time to perform inspection
FIR07-00046 INSP-Final Inspection2/19/20072/20/20072/21/2007 7:56:29 AMACANC
To be rescheduled since the fitter is sick today.
FIR06-00777 INSP-Sprinkler Rough-in2/20/20072/20/20072/20/2007 5:16:23 PMPPASS
The underground piping is ok to cover. The sprinkler piping for the first floor offices is ok to cover as well. Per Nick Anderson the extended coverage sidewall heads will operate off of the existing pipe size but will still be resubmitted.
BLD06-01803 FIRE-Alarm Testing2/20/20072/20/20072/20/2007 5:04:42 PMPCANC
Duplicate inspection
BLD06-03205 FIRE-Final Inspection2/16/20072/20/20072/20/2007 5:00:49 PMACANC
wrong inspection type called in.
BLD06-03211 FIRE-Final Inspection2/16/20072/20/20072/20/2007 5:00:21 PMACANC
wrong inspection type called in.
BLD06-03208 FIRE-Final Inspection2/16/20072/20/20072/20/2007 4:59:42 PMACANC
wrong inspection type called in.
BLD06-03207 FIRE-Final Inspection2/16/20072/20/20072/20/2007 4:58:06 PMACANC
wrong inspection type called in.
FIR07-00043 INSP-Final Inspection2/19/20072/20/20072/20/2007 4:55:46 PMPFAIL
No approved plans on site so no inspection was performed.
BLD06-01803 FIRE-Final Inspection2/16/20072/20/20072/20/2007 4:55:03 PMACANC
I notified the contractor that I would not perform the life safety inspection until both the fire alarm and fire sprinkler permits had been finaled.
FIR06-00591 INSP-Conference2/16/20072/20/20072/20/2007 2:44:30 PMPDONE
The roofing on the west end canopy is going to be permanently removed as well as the fire sprinkler protection.
BLD05-03042 FIRE-Final Inspection2/20/20072/20/20072/20/2007 2:17:06 PMPFAIL
Provide addresses at the street as discussed, mount and tag the fire extinguishers, provide signage for fire dept access and repair the smoke detector in building 938
FIR07-00131 INSP-Sprinkler Rough-in2/20/20072/20/20072/20/2007 1:37:10 PMPPASS
Sprinkler piping as installed is ok but I requested a tenting inspection prior to covering the piping. Mike is getting with the contractor to set it up next week.
FIR07-00119 INSP-Final Inspection2/20/20072/20/20072/20/2007 1:19:04 PMPPASS
permit finaled. I asked the contractor to provide a new inspection tag for the ant-freeze system.
MIS07-00023 FIR-Final2/16/20072/20/20072/20/2007 12:33:33 PMAPASS
Life safety finaled
FIR07-00012 INSP-Final Inspection2/19/20072/20/20072/20/2007 12:16:58 PMAPASS
Permit finaled. A/V candella corrected while I was on site.
FIR06-00954 INSP-Final Inspection2/16/20072/20/20072/20/2007 11:12:54 AMAPART
All items on the correction notice have been corrected except the alarm interconnections need verified.