BLD06-02677
| FIRE-Final Inspection | 2/19/2008 | 2/20/2008 | 2/21/2008 2:30:15 PM | A | FAIL |
|
|
No approved set of plans on site.Plan review notes require mixing room to be sprinklered, no sprinkler work has been completed per plan review notes. Could not complete inspection do to paint booth being used.KR
|
BLD07-00430
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 5:17:43 PM | P | NH |
|
|
No access to complete inspection, rescheduled per conversation with contractor.
|
FIR07-01051
| INSP-Sprinkler Rough-in | 2/20/2008 | 2/20/2008 | 2/20/2008 5:11:12 PM | P | PART |
|
|
UG fire supply line and remote FDC piping are approved for bury, need to install caps at the risers and seismic clearance method at the floor slab penetrations.
|
BLD07-00898
| FIRE-Final Inspection | 2/19/2008 | 2/20/2008 | 2/20/2008 4:36:46 PM | A | PASS |
|
|
Fire life safety per scope of permit work finaled.
|
BLD06-03527
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 4:13:31 PM | P | PART |
|
|
Final pending shell and core permit finals, also need to attatch closure at the west door to the exit corridor.
|
FIR07-00471
| INSP-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 4:12:14 PM | A | PASS |
|
|
Fire alarm permit work passed field testing.
|
FIR06-00540
| INSP-Sprinkler Rough-in | 2/19/2008 | 2/20/2008 | 2/20/2008 3:37:42 PM | A | PART |
|
|
OH installation for the plaza level branch lines and sprinklers as annotated on stamped plans is approved for cover, preliminary hydrostatic has been completed- will retest when the balance of the new main is finished.
|
FIR08-00037
| INSP-Sprinkler Rough-in | 2/18/2008 | 2/20/2008 | 2/20/2008 3:07:58 PM | P | PART |
|
|
See areas on approved plans okayed for cover, noted missing unistrut clamps at two locations on the 1 1/2 main, tie-in and EQ brace at the 2" main and 1 1/2 mains are not yet completed, need one upright installed at open office area south side, some noted items from previous inspection are finished, need to complete a hydrostatic test at the east office area new main and branch lines.
|
FIR07-00854
| INSP-Supply line flush | 2/19/2008 | 2/20/2008 | 2/20/2008 2:18:32 PM | P | CANC |
|
|
Inspection rescheduled per contractor due to coordination with United Water company.
|
FIR08-00086
| INSP-Final Inspection | 2/19/2008 | 2/20/2008 | 2/20/2008 2:16:26 PM | A | PASS |
|
|
Fire sprinkler work completed acceptable, inspection passed, permit finaled.
|
BLD08-00084
| FIRE-Final Inspection | 2/19/2008 | 2/20/2008 | 2/20/2008 1:31:05 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD07-02772
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 12:58:26 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD07-03122
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 12:57:39 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD07-02576
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 11:17:01 AM | A | PASS |
|
|
Fire life safety is acceptable pending installation of door hardware and signage at the east terrace door per review comments-to be complete prior to structural final as discussed. PFE has been certified, remainder of life safety items okayed.
|
BLD08-00060
| FIRE-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 11:09:04 AM | A | FAIL |
|
|
Lacking proper fire alarm notification coverage due to remodel work.
|
FIR07-01008
| INSP-Final Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 11:05:09 AM | P | PASS |
|
|
Fire alarm testing passed, noted two duct detectors have been deleted due to HVAC capacities below 2000 cfm.
|
FIR07-00946
| FIR-Aging Inspection | 2/20/2008 | 2/20/2008 | 2/20/2008 9:08:52 AM | | DEFR |
|
|
Pending field inspection request.
|