Inspections for the day of: Wednesday, February 20, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00107 INSP-Sprinkler Rough-in2/20/20082/20/20082/20/2008 5:45:11 PMPPASS
Underground flush passed.
FIR08-00077 INSP-Sprinkler Rough-in2/19/20082/20/20082/20/2008 5:44:23 PMPPASS
Underground supply piping is ok to cover
FIR07-00199 INSP-Final Inspection2/15/20082/20/20082/20/2008 5:42:31 PMAFAIL
System was completely tested. found that they were not ready to test duct detectors,Also found that sprinkler bell rings on general building alarm, not water flow. Mangates on outside of building did not release during fire alarm, gates are access to public way. KR
BLD06-02599 FIRE-Final Inspection2/18/20082/20/20082/20/2008 3:39:06 PMPPASS
Life safety passed.
FIR07-01013 INSP-Sprinkler Rough-in/Hydro2/19/20082/20/20082/20/2008 3:27:12 PMPPASS
The wet system and dry system hydro tests passed.
FIR08-00015 INSP-Sprinkler Rough-in/Hydro2/19/20082/20/20082/20/2008 3:26:13 PMPPASS
All piping except the second floor is ok to cover. Brian Johnson needs to approve the new piping arrangement. The dry system hydro test passed. The wet system hydro test failed.
FIR08-00107 INSP-Sprinkler Rough-in2/20/20082/20/20082/20/2008 2:21:29 PMAPASS
The underground supply piping is ok to cover.
FIR07-00578 INSP-Sprinkler Rough-in2/19/20082/20/20082/20/2008 2:15:56 PMACANC
To be rescheduled for tomorrow morning
BLD07-01770 FIRE-Final Inspection2/20/20082/20/20082/20/2008 2:02:43 PMAPASS
LIfe safety passed.
FIR08-00022 INSP-Sprinkler Rough-in/Hydro2/20/20082/20/20082/20/2008 8:48:41 AMAPASS
Permit finaled