Inspections for the day of: Wednesday, February 20, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00195 FIR-Aging Inspection2/20/20132/20/20132/28/2013 3:16:55 PM DEFR
I contacted Roy in Fire Prevention and he is going to follow up with the owner.
FIR12-00691 INSP-Sprinkler Rough-in2/20/20132/20/20132/20/2013 3:45:54 PMPPASS
See the city approved plans for locations where the sprinkler piping can be covered. Rick was going to follow up with the designer about the pipe route changes for the two mains and if they are going to effect the hydraulic calculations.
BLD12-02801 FIRE-Final Inspection2/20/20132/20/20132/20/2013 3:03:37 PMPPASS
Life safety passed. Sam and Bill Matter worked out the door hardware issues.
FIR13-00012 INSP-Final Inspection2/20/20132/20/20132/20/2013 2:27:00 PMPPASS
Permit finaled
FIR12-00574 INSP-Sprinkler Rough-in2/20/20132/20/20132/20/2013 2:19:01 PMPPART
The original "job site copy" of plans with review notes and data sheets needs to be on site at the next inspection. I gave the ok to cover on the west side exterior canopy. The south and east canopy have been covered without any piping inspection. The contractor is now removing plywood for an inspection to be scheduled for tomorrow. I spoke to Odie, with Steed Const. about covering prior to rough-in inspections. I did look at one interor area, marked in red on the plans, and noted three items. One is a retaining strap needs installed correctly, the other is flexible cplgs. are needed at the CMU wall penatration and riser nipply size and lenght has not been indicated on the plans for verification. Other than the exterior canopy inspection tomorrow, per Mark and I's dicussion the remaining building will be scheduled for monday.
BLD13-00032 FIRE-Final Inspection2/20/20132/20/20132/20/2013 12:44:29 PMPPASS
Life safety passed
BLD13-00116 FIRE-Final Inspection2/19/20132/20/20132/20/2013 9:34:25 AMAFAIL
Provide fire extinguisher with current inspection tag as discussed. Provide sticker over door and remove the thumbturn dead bolt at the exit. Keyed is ok.
FIR12-00694 INSP-Final Inspection2/19/20132/20/20132/20/2013 9:15:20 AMAPASS
Permit finaled
BLD12-02605 FIRE-Final Inspection2/19/20132/20/20132/20/2013 9:14:46 AMAPASS
Life safety passed
FIR13-00012 INSP-Final Inspection2/19/20132/20/20132/20/2013 9:14:07 AMACANC
There is a fees hold on this project. Fees need payed prior to another inspection.