FIR13-00629
| INSP-Final Inspection | 2/20/2014 | 2/20/2014 | 2/20/2014 3:36:30 PM | P | FAIL |
|
|
The fire alarm panel installed does not match data sheet or drawings. Wall layout does not match existing. Some audio/visual devices have been deleted. Audio/visual devices need to be added in other locations including the aisle ways in the warehouse. Plans need to be resubmitted showing the changes. No devices tested except the phone line #1 and #2 were verified.
|
BLD14-00158
| FIRE-Final Inspection | 2/19/2014 | 2/20/2014 | 2/20/2014 2:44:26 PM | P | FAIL |
|
|
Provide the correct size fire extinguisher with current inspection tag and provide plan review the corrected floor plan layout.
|
BLD14-00336
| FIRE-Final Inspection | 2/20/2014 | 2/20/2014 | 2/20/2014 12:24:54 PM | P | PART |
|
|
Temp occupancy approved for life safety
|
BLD14-00339
| FIRE-Final Inspection | 2/19/2014 | 2/20/2014 | 2/20/2014 12:23:58 PM | A | PART |
|
|
Temp. occupancy approved for life safety.
|
BLD14-00248
| FIRE-Final Inspection | 2/19/2014 | 2/20/2014 | 2/20/2014 10:49:09 AM | A | FAIL |
|
|
Provide fire extinguishers as discussed, provide missing exit signs in the warehouse, provide emergency lighting through-out, provide single action hardware on the exit doors as marked provide sprinkler system analasis and verification repairs have been completed, contact plan review about floor plan not matching.
|
FIR14-00096
| INSP-Sprinkler Rough-in/Hydro | 2/19/2014 | 2/20/2014 | 2/20/2014 10:13:47 AM | A | PASS |
|
|
Soffits as marked on the plans are ok to cover.
|
BLD13-03203
| FIRE-Final Inspection | 2/19/2014 | 2/20/2014 | 2/20/2014 8:56:18 AM | A | PASS |
|
|
life safety passed
|