FIR14-00708
| INSP-Sprinkler Rough-in | 2/20/2015 | 2/20/2015 | 2/20/2015 5:33:32 PM | P | PART |
|
|
Area F 1st floor living units passed rough-in inspection.
|
FIR14-00681
| INSP-Sprinkler Rough-in | 2/20/2015 | 2/20/2015 | 2/20/2015 5:32:15 PM | P | PART |
|
|
Overhead work at the sheetrock lid ceilings first floor area D east half to rated wall as annotated and dated on approved plans okay for cover.
|
FIR14-00903
| INSP-Final Inspection | 2/13/2015 | 2/20/2015 | 2/20/2015 2:51:01 PM | P | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR15-00063
| INSP-Sprinkler Rough-in/Hydro | 2/19/2015 | 2/20/2015 | 2/20/2015 1:32:04 PM | P | PART |
|
|
Overhead work passed inspection with the exception of missing coverage at the newly added gas fireplace in the master bedroom not shown on plans. UG fire supply line is not yet installed.
|
FIR14-00661
| INSP-Final Inspection | 2/19/2015 | 2/20/2015 | 2/20/2015 1:29:50 PM | P | PASS |
|
|
Verified approved plans. Points map to be posted today as agreed. Fire alarm permit finaled.
|
FIR14-00866
| INSP-Sprinkler Rough-in | 2/19/2015 | 2/20/2015 | 2/20/2015 1:28:18 PM | A | PART |
|
|
Partial rough-in for branchlines installed at the 3rd floor west side living units. Min. distance between heads is exceeded at five rooms -323,321,314,312,311 and 2nd floor 212. Drops are not yet installed at some locations.
|
FIR14-00918
| INSP-Final Inspection | 2/20/2015 | 2/20/2015 | 2/20/2015 11:03:01 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD14-03570
| FIRE-Final Inspection | 2/19/2015 | 2/20/2015 | 2/20/2015 11:02:22 AM | A | PASS |
|
|
C/N items verified for completion. Fire life safety passed.
|