ELE13-01235
| ELE-Aging Inspection | 2/20/2018 | 2/20/2018 | 2/21/2018 2:22:21 PM | | FAIL |
|
|
Still waiting on contractor
|
ELE15-01608
| Electrical Rough-In | 2/20/2018 | 2/20/2018 | 2/20/2018 2:45:46 PM | P | PASS |
|
|
James-ceiling Phone #: ###-#### Level 1 west offices not ready. Level 1 central offices and conference room grid rough in ok cover.
|
ELE17-04217
| Rough-In Permanent Service | 2/20/2018 | 2/20/2018 | 2/20/2018 2:16:32 PM | P | PASS |
|
|
Mitch Phone #: ###-#### Garage rough in ok cover p/s o/h n ok
|
ELE18-00398
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 1:41:54 PM | P | PART |
|
|
for temp // Jose Phone #: ###-#### Cubicals being installed. will call for final. TCO ok signed card
|
ELE18-00201
| Rough-In Permanent Service | 2/20/2018 | 2/20/2018 | 2/20/2018 1:17:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall Furnaca shall have a disconnecting means. Ryan stated will install lockout on breaker. Rough in ok cover p/s u/g n ok
|
ELE18-00202
| Rough-In Permanent Service | 2/20/2018 | 2/20/2018 | 2/20/2018 1:15:16 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall Furnace shall have a disconnecting means. Ryan stated will install lockout on breaker. Rough in ok cover p/s u/g n ok
|
ELE18-00649
| Rough-In Permanent Service | 2/19/2018 | 2/20/2018 | 2/20/2018 11:15:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Berthelot Rough in ok cover p/s u/g n ok
|
ELE17-03778
| Electrical Rough-In | 2/19/2018 | 2/20/2018 | 2/20/2018 10:25:16 AM | A | PASS |
|
|
Underground inspection call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott Feeder exterior conduits rough in ok cover.
|
ELE18-00550
| Electrical Rough-In | 2/19/2018 | 2/20/2018 | 2/20/2018 9:52:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Feeder in wall and bench receptacles rough in ok cover
|
ELE18-00204
| Final | 2/19/2018 | 2/20/2018 | 2/20/2018 9:19:30 AM | A | PASS |
|
|
This is for the shop and the side man door will be open. If you have any questions please feel free to contact Aaron ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
ELE18-00496
| Rough-In Permanent Service | 2/16/2018 | 2/20/2018 | 2/20/2018 9:01:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|