MEC18-00807
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 4:17:33 PM | P | PASS |
|
|
PLEASE CALL OUR LEAD INSTALLER DAKODA WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace AC CO ok
|
MEC18-00774
| Pressure Test | 2/20/2018 | 2/20/2018 | 2/20/2018 3:56:27 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- ok for backfill- need final called in when everything is running and done
|
MEC18-00804
| Rough-in | 2/20/2018 | 2/20/2018 | 2/20/2018 3:45:30 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- duct in crawl needs supported 4" clearance to ground, laying on ground- boots all need mastic to floor- need to install boot in closet for conditioned crawl- need to fix all rips and tears in armaflex- left correction notice front window
|
MEC18-00804
| Conference | 2/20/2018 | 2/20/2018 | 2/20/2018 3:42:57 PM | P | PASS |
|
|
fireples Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace R/I ok
|
MEC18-00804
| Pressure Test | 2/20/2018 | 2/20/2018 | 2/20/2018 3:42:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
|
MEC18-00792
| Pressure Test | 2/19/2018 | 2/20/2018 | 2/20/2018 3:11:23 PM | P | PASS |
|
|
installer Miguel ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 20lb gas pass- need to add range hood to permit details- call for final when range hood is installed
|
MEC18-00546
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 2:46:12 PM | P | PASS |
|
|
Please call Bill when heading over. ###-#### Thank you! Phone #: ###-#### Inspection requested via web by Ron Arnold- furnace AC gas piping CO ok
|
MEC18-00546
| Pressure Test | 2/20/2018 | 2/20/2018 | 2/20/2018 2:44:58 PM | P | PASS |
|
|
Please call Bill when heading over. ###-#### Phone #: ###-#### Inspection requested via web by Ron Arnold- 20lb gas pass
|
MEC18-00732
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 2:27:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jasmin Godina- need address posted visibly on house
|
MEC18-00764
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 2:17:21 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Devony Bullard- R/I ok
|
MEC18-00764
| Pressure Test | 2/19/2018 | 2/20/2018 | 2/20/2018 2:16:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Devony Bullard- 20lb gas pass
|
MEC18-00809
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 1:58:35 PM | P | PASS |
|
|
Inspection requested via web by Floyd Floyd Peek- 5lb flue pass- furnace coil CO ok
|
MEC18-00813
| Rough-in | 2/20/2018 | 2/20/2018 | 2/20/2018 1:23:09 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by Teresa Costello- still installing
|
MEC18-00813
| Pressure Test | 2/20/2018 | 2/20/2018 | 2/20/2018 1:22:48 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by Teresa Costello- still installing
|
MEC18-00800
| Rough-in | 2/20/2018 | 2/20/2018 | 2/20/2018 12:51:32 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need to finish allcondensate drains- unit 103 dryer vent at roof not attached
|
MEC18-00803
| Rough-in | 2/20/2018 | 2/20/2018 | 2/20/2018 12:50:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok-
|
MEC17-05641
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 11:19:27 AM | P | PASS |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok- card signed
|
MEC18-00783
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 11:06:10 AM | A | PASS |
|
|
courtesy duct seal inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need to install 2 taps with direction of air flow 1 return 1 supply- seal ok- ok to insulate- GC checking on address this is for 7576 victory rough in
|
MEC18-00766
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 10:36:12 AM | A | FAIL |
|
|
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero- need to seal around plywood at ceiling so no insulation can fall into fireplace chase
|
MEC18-00806
| Final | 2/20/2018 | 2/20/2018 | 2/20/2018 10:33:54 AM | P | CANC |
|
|
Thank you! >> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek
|
MEC18-00734
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 10:32:08 AM | A | FAIL |
|
|
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero- need to support flue pipe per manufactors install instructions- need to seal plywood at ceiling around outside so no insulation can fall into fireplace chase
|
MEC17-02216
| Final | 2/19/2018 | 2/20/2018 | 2/20/2018 10:17:45 AM | A | PART |
|
|
Final - call Luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- dryers ok- need to seal outside penetration water tight- need airbalance report onsite to final out
|
MEC18-00765
| Rough-in | 2/16/2018 | 2/20/2018 | 2/20/2018 9:55:09 AM | A | PASS |
|
|
Home Owner Rod Colton and his contact number is ###-#### Phone #: ###-#### Inspection requested via web by Jasmin Godina- R/I on fireplace ok- pressure test failed to range
|
MEC18-00765
| Pressure Test | 2/16/2018 | 2/20/2018 | 2/20/2018 9:54:09 AM | A | FAIL |
|
|
Home Owner Rod Colton and his contact number is ###-#### Phone #: ###-#### Inspection requested via web by Jasmin Godina- 20lb gas pass to fire place- 20lb gas fail to range
|
MEC17-05774
| Final | 2/16/2018 | 2/20/2018 | 2/20/2018 9:35:57 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- will schedule duct blast at another time
|
MEC17-05774
| Conference | 2/16/2018 | 2/20/2018 | 2/20/2018 9:35:30 AM | A | CANC |
|
|
Blast witness at 9:30 Please Phone #: ###-#### Inspection requested via web by Randy Hart- will reschedule per phone call to contractor
|
MEC18-00795
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 9:16:24 AM | A | DONE |
|
|
Please call Dustin, thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
MEC18-00795
| DOC - Permit Expired | 2/20/2018 | 2/20/2018 | 2/20/2018 9:16:15 AM | P | PASS |
|
|
Please call Dustin, thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- this inspection needs to be done thru the state
|
MEC18-00796
| Rough-in | 2/19/2018 | 2/20/2018 | 2/20/2018 9:15:41 AM | A | DONE |
|
|
please call Dustin, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
MEC18-00796
| DOC - Permit Expired | 2/20/2018 | 2/20/2018 | 2/20/2018 9:15:17 AM | P | PASS |
|
|
please call Dustin, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- this inspection needs to be done with state-
|
MEC17-01470
| Mec-Aging Inspection | 2/20/2018 | 2/20/2018 | 2/20/2018 9:14:40 AM | | PEND |
|
|
contractor will schedule final
|
MEC18-00774
| Pressure Test | 2/16/2018 | 2/20/2018 | 2/20/2018 8:54:15 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt- guage at 3 psi
|
MEC17-05703
| Final | 2/15/2018 | 2/20/2018 | 2/20/2018 8:47:18 AM | A | PASS |
|
|
Please have inspector call tenant Scott when in route to home ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd- furnace CO ok
|
MEC18-00616
| Pressure Test | 2/16/2018 | 2/20/2018 | 2/20/2018 8:27:57 AM | A | PASS |
|
|
Please call Shannon with any issues Phone #: ###-#### Inspection requested via web by Zach Moran- 20lb gas pass
|
MEC18-00616
| Rough-in | 2/16/2018 | 2/20/2018 | 2/20/2018 8:27:34 AM | A | PASS |
|
|
Please call Shannon with any issues Phone #: ###-#### Inspection requested via web by Zach Moran- R/I ok
|