Inspections for the day of: Tuesday, February 20, 2018.
Number of inspections: 29
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDan Ediger
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM17-02424 PLM-Aging Inspection2/20/20182/20/20182/23/2018 3:06:50 PM PEND
under snow check back
PLM18-00725 Final2/20/20182/20/20182/20/2018 5:30:40 PMPPART
Michael Phone #: ###-####. The water service ok to cover. Final after pvb is certified.
PLM18-00691 Plumbing Rough-in2/16/20182/20/20182/20/2018 4:53:03 PMPNH
JOB # 19572 Phone #: ###-#### Inspection requested via web by Ann Marie Reyes. Job locked. I rescheduled for tomorrow am.
PLM18-00706 Final2/19/20182/20/20182/20/2018 4:33:55 PMPPASS
Please call general contractor Dan Hemmer at ###-#### when you are on the way and he will meet you out there for access. If there are any other issues please let me know. Thanks. Phone #: ###-#### Inspection requested via web by Josh Johnson
PLM17-04398 Final2/18/20182/20/20182/20/2018 4:23:47 PMPPASS
Phone #: ###-#### Inspection requested via web by Frank Young
PLM17-05049 Plumbing Rough-in2/20/20182/20/20182/20/2018 4:14:28 PMPPASS
Had to replace all my water lines over the last 3 days when my Polybutylene pipes failed. Want to get a rough in inspection and extend my permit Phone #: ###-#### Inspection requested via web by Tyler Miller
PLM18-00663 Water and/or Sewer2/20/20182/20/20182/20/2018 3:50:24 PMPPART
Water only - Daryl Phone #: ###-####
Replace the pvc female adapter at the meter stinger connection to a male sch. 80 fitting and retest. The rest of the service is ok to cover
PLM18-00718 Water and/or Sewer2/19/20182/20/20182/20/2018 3:20:03 PMPPART
PLEASE INSPECT AS LATE AS POSSIBLE. PLUMBER ON SITE BRIAN ###-#### Phone #: ###-#### Inspection requested via web by Chris Field. OK to cover. Need backflow certs.
PLM17-05053 Plumbing Rough-in2/16/20182/20/20182/20/2018 2:52:27 PMPPASS
JOB # 51193 Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM17-05102 Final2/20/20182/20/20182/20/2018 2:27:24 PMPPASS
PLM17-05102 DOC - Permit Finaled2/20/20182/20/20182/20/2018 2:27:13 PMPPASS
PLM17-04940 Final2/20/20182/20/20182/20/2018 1:43:39 PMPPASS
Lock box code on front door is 3975. Home is vacant. Phone #: ###-#### Inspection requested via web by Scott Sparrell
PLM18-00712 Water Heater Final2/19/20182/20/20182/20/2018 1:25:29 PMAFAIL
Anytime is fine. Please call David York when on way ###-#### or the Main office line ###-#### Phone #: ###-#### Inspection requested via web by Scott Ferguson.
The t&p drain must have an air gap and strap so it's ridgid over the drain. Call when complete
PLM18-00302 Water and/or Sewer2/20/20182/20/20182/20/2018 1:03:47 PMPPASS
David-sewer line only Phone #: ###-####.
Drain to the sewer ok to cover
PLM17-05008 Final2/20/20182/20/20182/20/2018 12:50:11 PMAFAIL
Door code 36987
The lock box is hard to open but it works Phone #: ###-#### Inspection requested via web by MICHAEL BYERS.
Pipe the t&p to an approved drain with an air gap.
Strap th ewater heater to the wall.
PLM18-00674 Water and/or Sewer2/19/20182/20/20182/20/2018 12:34:20 PMPFAIL
Phone #: ###-#### Inspection requested via web by David Snow.
Must use drainage fittings not presuure fittings.
PLM17-05072 Final2/19/20182/20/20182/20/2018 12:16:31 PMAFAIL
Garage code 1331 Phone #: ###-#### Inspection requested via web by Aarin Van Curen
1. The water heater is leaking into the pan.
2. The laundry faucet requires a vacuum breaker.
PLM18-00644 Water Heater Final2/16/20182/20/20182/20/2018 12:02:18 PMAPASS
Owner is Ellisea Robbins. Please call on way ###-#### Phone #: ###-#### Inspection requested via web by Heidi Lukecart
PLM18-00641 Other2/19/20182/20/20182/20/2018 11:53:45 AMAPASS
Request an onsite consult for a structural condition issue Phone #: ###-#### Inspection requested via web by Jeremy Paxman
PLM18-00599 Groundwork2/16/20182/20/20182/20/2018 11:38:34 AMAPASS
ANDY IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
PLM18-00721 Water and/or Sewer2/19/20182/20/20182/20/2018 11:13:57 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brett Simmons. failed waste test.
PLM18-00699 Final2/16/20182/20/20182/20/2018 11:03:58 AMAPASS
Mary Jackson is designer and contact-###-#### Phone #: ###-#### Inspection requested via web by Heidi Lukecart. no rough-in inspectioin requested final only
PLM18-00697 Water Heater Final2/16/20182/20/20182/20/2018 10:42:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Chris Field
PLM17-01613 PLM-Aging Inspection2/20/20182/20/20182/20/2018 10:33:04 AM PASS
PLM17-01613 DOC - Permit Expired2/20/20182/20/20182/20/2018 10:32:54 AMPCANC
failed to respond
PLM17-01432 Plumbing Rough-in2/19/20182/20/20182/20/2018 10:30:58 AMAPART
Commercial Tower Rough In. If there are any questions please contact Larry J. at ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann.
Burn tower.
2nd floor, ceiling and floor lp test ok.
3rd floor, floor lp pressure test ok.
East lp riser pressure test ok.
whole tower h2o pressure test ok.
PLM17-05102 Final2/18/20182/20/20182/20/2018 10:06:25 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jason Brashears
Install a rp backflow prevention assembly at the pitcher washer due to a low water inlet.
Provide air gaps of 2x the pipe diameter on all indirect waste lines that don't already have an airgap.
PLM17-05084 Final2/18/20182/20/20182/20/2018 10:04:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Jason Brashears
PLM17-05084 DOC - Permit Finaled2/20/20182/20/20182/20/2018 10:02:33 AMPPASS