Inspections for the day of: Thursday, February 20, 2020.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00679 Pressure Test2/19/20202/20/20202/20/2020 3:42:08 PMPPASS
flue test witness at 3 to 330- - furnace only co ok- 5lb flue pass
MEC20-00656 Rough-in2/19/20202/20/20202/20/2020 3:16:49 PMPPASS
CHRISTINA ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
MEC20-00688 Final2/19/20202/20/20202/20/2020 2:41:49 PMPPASS
Please call Chuck when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC20-00709 Final2/19/20202/20/20202/20/2020 2:41:11 PMPPASS
Please call Craig when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
PLM20-00645 Final2/19/20202/20/20202/20/2020 2:36:15 PMPPASS
Please call Chuck on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
PLM20-00645 Pressure Test2/19/20202/20/20202/20/2020 1:51:39 PMPCANC
Please call Chuck on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no test needed unconditioned space
MEC20-00688 Pressure Test2/19/20202/20/20202/20/2020 1:51:13 PMPCANC
Please call Chuck on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no test needed
MEC20-00649 Rough-in2/20/20202/20/20202/20/2020 1:10:32 PMPPASS
R/I ok
MEC20-00649 Pressure Test2/20/20202/20/20202/20/2020 1:09:33 PMPPASS
20lb gas pass tagged meter location- 5lb flue pass
MEC20-00713 Rough-in2/19/20202/20/20202/20/2020 10:58:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Kristy Watson- R/I ok
MEC20-00713 Pressure Test2/20/20202/20/20202/20/2020 10:56:02 AMPPASS
Phone #: ###-#### Inspection requested via web by Kristy Watson- 20lb gas pass tagged meter location- 5lb flue pass
MEC20-00631 Rough-in2/18/20202/20/20202/20/2020 10:21:33 AMAFAIL
Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need to fix all rips and tears in arma flex in attic bare copper showing
MEC20-00631 Pressure Test2/18/20202/20/20202/20/2020 10:20:48 AMAPASS
Builder ###-#### - HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- 20lb gas pass tagged meter location- 5lb flue pass
MEC20-00649 Rough-in2/18/20202/20/20202/20/2020 9:52:09 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
1- flue test at zero-
2- need to support gas line in garage
3- need to fix rips and tears in arma flex in attic bare copper showing and needs more supports
4- need to seal metal 90 to plastic fitting on exhaust fans

went over with foreman onsite- i reschedule for pm per pur conversation he will get items fixed
MEC20-00649 Pressure Test2/18/20202/20/20202/20/2020 9:49:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- flue gauge at zero- i reschedule this for pm- went over issue with foreman onsite
MEC20-00669 Final2/17/20202/20/20202/20/2020 9:10:51 AMAFAIL
Homeowner Abdul Samad ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- need to support gas line at furnace between flex gas connector and furnace- need locking caps on a/c service ports
MEC20-00665 Final2/20/20202/20/20202/20/2020 8:54:46 AMAPASS
locking caps installed
MEC20-00352 Final2/19/20202/20/20202/20/2020 8:43:03 AMAPASS
please call Ernie Prior to arrival for access.

thanks,
Phone #: ###-#### Inspection requested via web by Nicholas Paige- final ok- card signed
MEC19-03480 Mec-Aging Inspection2/20/20202/20/20202/20/2020 7:50:01 AM FAIL
contractor needs to schedule inspection no activity since issuing permit- permit will expire next aging if no activity
MEC19-03475 Mec-Aging Inspection2/20/20202/20/20202/20/2020 7:49:06 AM FAIL
contractor needs to schedule inspection on pellet stove no activity since permit issued- permit will expire next aging if no activity
MEC10-02322 Mec-Aging Inspection2/20/20202/20/20202/20/2020 7:48:11 AM FAIL
no calls for inspection
MEC19-01866 Mec-Aging Inspection2/20/20202/20/20202/20/2020 7:46:20 AM CANC
permit expired
MEC19-01866 DOC - Permit Expired2/20/20202/20/20202/20/2020 7:46:08 AMAPASS
no calls no activity- permit expired