Inspections for the day of: Wednesday, February 21, 2001.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00297 INSP-Conference2/20/20012/21/20012/21/2001 12:00:00 AMAPART
###-#### discussed alarm testing and detector placement per alarm plans 2/21/2001 5:26:34 PM
BLD00-03573 FIRE-Final Inspection2/20/20012/21/20012/21/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 02/20/2001 at 16:27:49. Contact: ###-####. c/n issued - need sprinkler monitoring; exit door hardware; landing at new door; sprinklers in restrooms 2/21/2001 11:13:50 AM
FIR00-00513 INSP-Sprinkler Rough-in/Hydro2/21/20012/21/20012/21/2001 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 02/21/2001 at 09:32:15. Contact: ###-####. hydro test okay for overhead of both dry and wet systems; still need to hydro the underground 2/21/2001 5:27:17 PM
BLD00-03654 FIRE-Final Inspection2/21/20012/21/20012/21/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 2/21/2001 2:00:44 PM
BLD00-03654 FIRE-Alarm Testing2/20/20012/21/20012/21/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 02/20/2001 at 15:48:20. Contact: ###-####.