Inspections for the day of: Tuesday, February 21, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS06-00033 FIR-Final2/21/20062/21/20062/21/2006 5:34:00 PMPFAIL
Sprinkler heads at some locations are overspaced off adjacent walls, two heads do not meet the minimum spacing requirements, a fire sprinkler permit will be necessary to complete the modifications.
FIR06-00088 INSP-Final Inspection2/13/20062/21/20062/21/2006 5:30:59 PMAPART
The hood suppression system functioned under test conditions, however the following items need to be addressed prior to final approval; provide a junction box for the power supply adjacent to the Ansul cabinet, the hood canopy must meet distance requirements for a minimum 6" extension beyond the cooking surface edge, holes in the hood must be properly sealed, where buildings are equipped with a fire alarm panel the hood suppression system must be monitored.
MIS06-00034 FIR-Final2/21/20062/21/20062/21/2006 4:22:13 PMPPASS
Fire life safety is acceptable, sign above door stating "this door to remain unlocked while building is occupied" to be verified at final.
FIR05-00620 INSP-Supply line flush2/21/20062/21/20062/21/2006 3:09:57 PMPPART
United Water on site to turn valve for UG fire supply line flushing, flush performed satisfactory.
FIR05-00724 INSP-Sprinkler Rough-in2/17/20062/21/20062/21/2006 3:06:21 PMAPART
Changes at two locations for the overhead rough-in at the deleted closet and added sw are acceptable, RI good for cover.
FIR05-00854 INSP-Sprinkler Rough-in2/17/20062/21/20062/21/2006 11:42:08 AMAPART
Lacking proper coverage at one "closet " area on the first floor, tenting has been adjusted at one bedroom location, the remainder of overhead rough-in is good for cover, possible light fixture obstructions at certain locations depending on the fixture dimentions.