MIS06-00033
| FIR-Final | 2/21/2006 | 2/21/2006 | 2/21/2006 5:34:00 PM | P | FAIL |
|
|
Sprinkler heads at some locations are overspaced off adjacent walls, two heads do not meet the minimum spacing requirements, a fire sprinkler permit will be necessary to complete the modifications.
|
FIR06-00088
| INSP-Final Inspection | 2/13/2006 | 2/21/2006 | 2/21/2006 5:30:59 PM | A | PART |
|
|
The hood suppression system functioned under test conditions, however the following items need to be addressed prior to final approval; provide a junction box for the power supply adjacent to the Ansul cabinet, the hood canopy must meet distance requirements for a minimum 6" extension beyond the cooking surface edge, holes in the hood must be properly sealed, where buildings are equipped with a fire alarm panel the hood suppression system must be monitored.
|
MIS06-00034
| FIR-Final | 2/21/2006 | 2/21/2006 | 2/21/2006 4:22:13 PM | P | PASS |
|
|
Fire life safety is acceptable, sign above door stating "this door to remain unlocked while building is occupied" to be verified at final.
|
FIR05-00620
| INSP-Supply line flush | 2/21/2006 | 2/21/2006 | 2/21/2006 3:09:57 PM | P | PART |
|
|
United Water on site to turn valve for UG fire supply line flushing, flush performed satisfactory.
|
FIR05-00724
| INSP-Sprinkler Rough-in | 2/17/2006 | 2/21/2006 | 2/21/2006 3:06:21 PM | A | PART |
|
|
Changes at two locations for the overhead rough-in at the deleted closet and added sw are acceptable, RI good for cover.
|
FIR05-00854
| INSP-Sprinkler Rough-in | 2/17/2006 | 2/21/2006 | 2/21/2006 11:42:08 AM | A | PART |
|
|
Lacking proper coverage at one "closet " area on the first floor, tenting has been adjusted at one bedroom location, the remainder of overhead rough-in is good for cover, possible light fixture obstructions at certain locations depending on the fixture dimentions.
|