Inspections for the day of: Wednesday, February 21, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00956 INSP-Sprinkler Rough-in2/20/20072/21/20072/22/2007 10:03:28 PMAPASS
Inspection was for building C. Rough to cover for third floor passed, Attic/dry system pipe passed, first and second floor main piping EQ restraints and hanger assemblies passed, first and second floor rough to cover passed. The FDC location is in question. Brian asked the general/Dale to supply PDS with a new proposed layout for review.
FIR06-00499 INSP-Final Inspection2/20/20072/21/20072/21/2007 5:05:31 PMPCANC
Inspection to be rescheduled due to time constraints.
BLD06-02969 FIRE-Final Inspection2/21/20072/21/20072/21/2007 5:04:12 PMPPASS
Life safety finaled
MIS07-00001 FIR-Final2/20/20072/21/20072/21/2007 4:00:00 PMPPASS
life safety passed
FIR06-00755 INSP-Sprinkler Rough-in/Hydro2/20/20072/21/20072/21/2007 2:20:02 PMAPASS
Underground hydro test passed. Contractor had to pump system back up to over 200lbs as I waited to begin test.
FIR05-00536 INSP-Sprinkler Rough-in2/20/20072/21/20072/21/2007 2:15:23 PMAPASS
See the city approved plans for locations where the piping above hardlids is ok to cover.
FIR06-00952 INSP-Final Inspection2/21/20072/21/20072/21/2007 1:41:06 PMPPART
Sprinkler piping is ok to cover but one head as marked on the plans was modified but is piped from an outlet that already has a drop on it. This head is shown on the plans as being piped from a mechanical tee. As per policy the two heads from a single 1" outlet is not allowed unless certain conditions have been met. Prove conditions or install as per the plans.
BLD06-03118 FIRE-Final Inspection2/20/20072/21/20072/21/2007 1:10:51 PMAPASS
Life safety finaled. Items on correction notice have been corrected.
FIR07-00101 INSP-Final Inspection2/21/20072/21/20072/21/2007 12:52:29 PMPPASS
The pendant in question is actually a different manufacture but is an extended coverage pendant as approved.. Permit finaled
BLD05-03043 FIRE-Final Inspection2/20/20072/21/20072/20/2007 2:43:07 PMAFAIL
Provide addresses at the street as discussed, mount and tag the fire extinguishers, provide signage for fire dept access and repair the smoke detector in building 938