FIR06-00956
| INSP-Sprinkler Rough-in | 2/20/2007 | 2/21/2007 | 2/22/2007 10:03:28 PM | A | PASS |
|
|
Inspection was for building C. Rough to cover for third floor passed, Attic/dry system pipe passed, first and second floor main piping EQ restraints and hanger assemblies passed, first and second floor rough to cover passed. The FDC location is in question. Brian asked the general/Dale to supply PDS with a new proposed layout for review.
|
FIR06-00499
| INSP-Final Inspection | 2/20/2007 | 2/21/2007 | 2/21/2007 5:05:31 PM | P | CANC |
|
|
Inspection to be rescheduled due to time constraints.
|
BLD06-02969
| FIRE-Final Inspection | 2/21/2007 | 2/21/2007 | 2/21/2007 5:04:12 PM | P | PASS |
|
|
Life safety finaled
|
MIS07-00001
| FIR-Final | 2/20/2007 | 2/21/2007 | 2/21/2007 4:00:00 PM | P | PASS |
|
|
life safety passed
|
FIR06-00755
| INSP-Sprinkler Rough-in/Hydro | 2/20/2007 | 2/21/2007 | 2/21/2007 2:20:02 PM | A | PASS |
|
|
Underground hydro test passed. Contractor had to pump system back up to over 200lbs as I waited to begin test.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 2/20/2007 | 2/21/2007 | 2/21/2007 2:15:23 PM | A | PASS |
|
|
See the city approved plans for locations where the piping above hardlids is ok to cover.
|
FIR06-00952
| INSP-Final Inspection | 2/21/2007 | 2/21/2007 | 2/21/2007 1:41:06 PM | P | PART |
|
|
Sprinkler piping is ok to cover but one head as marked on the plans was modified but is piped from an outlet that already has a drop on it. This head is shown on the plans as being piped from a mechanical tee. As per policy the two heads from a single 1" outlet is not allowed unless certain conditions have been met. Prove conditions or install as per the plans.
|
BLD06-03118
| FIRE-Final Inspection | 2/20/2007 | 2/21/2007 | 2/21/2007 1:10:51 PM | A | PASS |
|
|
Life safety finaled. Items on correction notice have been corrected.
|
FIR07-00101
| INSP-Final Inspection | 2/21/2007 | 2/21/2007 | 2/21/2007 12:52:29 PM | P | PASS |
|
|
The pendant in question is actually a different manufacture but is an extended coverage pendant as approved.. Permit finaled
|
BLD05-03043
| FIRE-Final Inspection | 2/20/2007 | 2/21/2007 | 2/20/2007 2:43:07 PM | A | FAIL |
|
|
Provide addresses at the street as discussed, mount and tag the fire extinguishers, provide signage for fire dept access and repair the smoke detector in building 938
|