BLD11-02505
| FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 3:45:50 PM | P | FAIL |
|
|
The emergency lighting and exit signs have been repaired except for the two exit discharge lights and the emergency lights at the main northeast exit. Rescheduled for tomorrow morning.
|
BLD11-01422
| FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 3:21:22 PM | P | PASS |
|
|
life safety passed
|
BLD12-00206
| FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 2:42:10 PM | P | PASS |
|
|
Life safety passed. Julie had removed the retail from the back area.
|
BLD12-00206
| FIRE-Conference | 2/17/2012 | 2/21/2012 | 2/21/2012 2:39:45 PM | A | DONE |
|
|
julie Phone #: ###-####
|
FIR12-00092
| INSP-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 2:25:12 PM | P | PASS |
|
|
permit finaled
|
BLD11-00232
| FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 2:01:55 PM | P | PASS |
|
|
life safety passed.
|
FIR11-00371
| INSP-Sprinkler Rough-in | 2/21/2012 | 2/21/2012 | 2/21/2012 1:22:18 PM | P | PASS |
|
|
Two additional rooms are ok for cover. See the city approved plans.
|
FIR11-00631
| INSP-Sprinkler Rough-in | 2/21/2012 | 2/21/2012 | 2/21/2012 11:06:21 AM | P | PART |
|
|
This is for a 24 hr air test. Test was started at 11:00 with 43 psi on the guage. I asked Tom to schedule the follow up for tomorrow.
|
BLD12-00012
| FIRE-Final Inspection | 2/20/2012 | 2/21/2012 | 2/21/2012 11:00:11 AM | A | PASS |
|
|
Life safety passed.
|
FIR12-00073
| INSP-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 10:59:54 AM | P | PASS |
|
|
Permit finaled.
|
BLD11-02505
| FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 10:59:29 AM | A | FAIL |
|
|
Provide exit discharge lighting over the two northeast exterior exit doors per plan review, repair the emergency light just inside the main exit doors, repair the emergency light on the east side of the kitchen, provide the missing exit sign in the kitchen.
|
FIR11-00611
| INSP-Final Inspection | 2/19/2012 | 2/21/2012 | 2/21/2012 10:57:34 AM | A | PASS |
|
|
Permit finaled. The ceiling tile in the adjoining space was being installed.
|
FIR12-00072
| INSP-Final Inspection | 2/17/2012 | 2/21/2012 | 2/21/2012 10:57:01 AM | A | PASS |
|
|
Permit finaled.
|
FIR12-00051
| INSP-Final Inspection | 2/17/2012 | 2/21/2012 | 2/21/2012 10:46:05 AM | A | PASS |
|
|
Permit finaled. The hood suppression system functioned correctly.
|