Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01932 ELE-Aging Inspection2/21/20142/21/20142/26/2014 4:15:46 PM DONE
No contact available
ELE11-00879 ELE-Aging Inspection2/21/20142/21/20142/26/2014 10:35:40 AM DONE
Still under construction
ELE13-03173 Final2/20/20142/21/20142/21/2014 4:15:48 PMPPASS
Phone #: ###-#### >> Inspection requested via web by mike brown final ok
ELE14-00422 Rough-In Permanent Service2/21/20142/21/20142/21/2014 3:30:49 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman rough in ok for cover p/s u/g n ok
ELE13-03066 Electrical Rough-In2/21/20142/21/20142/21/2014 2:58:56 PMPPART
ceiling cover 1st floor Phone #: ###-#### >> Inspection requested via web by Karl Paige all ok except open j box in waiting room and strapping of mc cable within 12" of box and seismic on fixtures in waiting room 132. ok for borders in ceiling.
GCE14-00027 GCE-Final2/21/20142/21/20142/21/2014 2:24:49 PMPFAIL
Greg ###-#### 352.46-bushing required for pvc conduit. 300.4-where raceways contain #4 or larger. these conductors shall be protected from abrasion. 300.5-direct burial conductors shall be 18" minimum depth.
GCE13-00181 GCE-Rough-In2/21/20142/21/20142/21/2014 2:06:08 PMPPASS
Mark ###-####
Ceiling for fixtures bath ceiling ok for cover. Mc cable to womens light fixture, jacket separated.
ELE14-00142 Rough-In Permanent Service2/20/20142/21/20142/21/2014 12:58:44 PMPPASS
Wall Rough-in Inspection >> Inspection requested via web by Kevin Perez service not ready. house rough in ok for cover.
ELE13-03391 Final2/20/20142/21/20142/21/2014 12:09:12 PMAPASS
Steven Phone #: ###-#### final ok
ELE13-01480 Final2/20/20142/21/20142/21/2014 11:45:28 AMAFAIL
Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 314.20 Outside lights, if boxes are recessed more than 1/4" plaster ring shall be installed. 314.23 non mettalic boxes shall be securily mounted (oven). 230.77-service disconnect shall be legibly identified.
ELE14-00417 Temporary Service2/20/20142/21/20142/21/2014 10:17:58 AMAPASS
Temp pole is in Allie next to shed Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk t/s o/h n ok
ELE13-03160 Electrical Rough-In2/20/20142/21/20142/21/2014 9:29:56 AMAPASS
Ceiling Cover. Desk number ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Lee phase 2 ceiling grid ok for cover
ELE13-03452 Final2/20/20142/21/20142/21/2014 9:05:35 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman 210.8 all 120 volt receptacle outlets located in kitchen shall have GFCI protection. 250.132-isolated sections of metal raceway shall be connected to equipment grounding conductor. Boiler wiring not complete.