ELE11-01932
| ELE-Aging Inspection | 2/21/2014 | 2/21/2014 | 2/26/2014 4:15:46 PM | | DONE |
|
|
No contact available
|
ELE11-00879
| ELE-Aging Inspection | 2/21/2014 | 2/21/2014 | 2/26/2014 10:35:40 AM | | DONE |
|
|
Still under construction
|
ELE13-03173
| Final | 2/20/2014 | 2/21/2014 | 2/21/2014 4:15:48 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by mike brown final ok
|
ELE14-00422
| Rough-In Permanent Service | 2/21/2014 | 2/21/2014 | 2/21/2014 3:30:49 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman rough in ok for cover p/s u/g n ok
|
ELE13-03066
| Electrical Rough-In | 2/21/2014 | 2/21/2014 | 2/21/2014 2:58:56 PM | P | PART |
|
|
ceiling cover 1st floor Phone #: ###-#### >> Inspection requested via web by Karl Paige all ok except open j box in waiting room and strapping of mc cable within 12" of box and seismic on fixtures in waiting room 132. ok for borders in ceiling.
|
GCE14-00027
| GCE-Final | 2/21/2014 | 2/21/2014 | 2/21/2014 2:24:49 PM | P | FAIL |
|
|
Greg ###-#### 352.46-bushing required for pvc conduit. 300.4-where raceways contain #4 or larger. these conductors shall be protected from abrasion. 300.5-direct burial conductors shall be 18" minimum depth.
|
GCE13-00181
| GCE-Rough-In | 2/21/2014 | 2/21/2014 | 2/21/2014 2:06:08 PM | P | PASS |
|
|
Mark ###-#### Ceiling for fixtures bath ceiling ok for cover. Mc cable to womens light fixture, jacket separated.
|
ELE14-00142
| Rough-In Permanent Service | 2/20/2014 | 2/21/2014 | 2/21/2014 12:58:44 PM | P | PASS |
|
|
Wall Rough-in Inspection >> Inspection requested via web by Kevin Perez service not ready. house rough in ok for cover.
|
ELE13-03391
| Final | 2/20/2014 | 2/21/2014 | 2/21/2014 12:09:12 PM | A | PASS |
|
|
Steven Phone #: ###-#### final ok
|
ELE13-01480
| Final | 2/20/2014 | 2/21/2014 | 2/21/2014 11:45:28 AM | A | FAIL |
|
|
Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 314.20 Outside lights, if boxes are recessed more than 1/4" plaster ring shall be installed. 314.23 non mettalic boxes shall be securily mounted (oven). 230.77-service disconnect shall be legibly identified.
|
ELE14-00417
| Temporary Service | 2/20/2014 | 2/21/2014 | 2/21/2014 10:17:58 AM | A | PASS |
|
|
Temp pole is in Allie next to shed Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk t/s o/h n ok
|
ELE13-03160
| Electrical Rough-In | 2/20/2014 | 2/21/2014 | 2/21/2014 9:29:56 AM | A | PASS |
|
|
Ceiling Cover. Desk number ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Lee phase 2 ceiling grid ok for cover
|
ELE13-03452
| Final | 2/20/2014 | 2/21/2014 | 2/21/2014 9:05:35 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman 210.8 all 120 volt receptacle outlets located in kitchen shall have GFCI protection. 250.132-isolated sections of metal raceway shall be connected to equipment grounding conductor. Boiler wiring not complete.
|