Inspections for the day of: Friday, February 21, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01935 FIRE-Final Inspection2/20/20142/21/20142/21/2014 5:11:05 PMPPART
Final pending paving/site access. Remainder of fire life safety passed.
FIR14-00100 INSP-Sprinkler Rough-in2/20/20142/21/20142/21/2014 5:08:21 PMPPART
OH rough-in approved for cover.
FIR14-00103 INSP-Sprinkler Rough-in2/21/20142/21/20142/21/2014 5:06:41 PMPPART
UG fire supply line ductile riser and stub to a point 9' beyond the stem wall approved for bury.
BLD13-03477 FIRE-Final Inspection2/21/20142/21/20142/21/2014 2:01:15 PMPPASS
Fire life safety passed.
FIR14-00048 INSP-Final Inspection2/18/20142/21/20142/21/2014 1:11:58 PMPFAIL
Noted insufficient coverage at four areas, one relocated and three added appliances not shown on plans or included in the calcs, need cd setting adjustment or devices per plan at the boutique. Resubmit plans to match changes and field installation.
FIR13-00664 INSP-Final Inspection2/20/20142/21/20142/21/2014 1:02:57 PMAPASS
Fire sprinkler permit finaled.
BLD13-02860 FIRE-Final Inspection2/20/20142/21/20142/21/2014 1:00:47 PMAPASS
C/N items verified. Fire life safety passed. *Note- fire sprinkler coverage at the shell areas to be maintained at new demising walls as discussed on site.
FIR14-00021 INSP-Final Inspection2/21/20142/21/20142/21/2014 12:57:55 PMAPASS
C/N items finished. Fire sprinkler permit finaled.
FIR13-00582 INSP-Final Inspection2/20/20142/21/20142/21/2014 12:55:32 PMAPART
Blocked upright head at the SW corner, remove foil at uprights, not all areas accessible for inspection due to flooring install underway.
FIR13-00706 INSP-Final Inspection2/20/20142/21/20142/21/2014 11:07:17 AMAPART
Final pending foam, escutcheon at the cooler dry pendent, field ceiling tile install.
FIR14-00079 INSP-Final Inspection2/20/20142/21/20142/21/2014 11:04:56 AMAPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
FIR14-00066 INSP-Final Inspection2/13/20142/21/20142/21/2014 11:03:20 AMAPASS
Scope of fire alarm work completed and passed functional testing. Permit finaled.
FIR11-00228 INSP-Final Inspection2/20/20142/21/20142/21/2014 9:28:27 AMAPASS
Remainder of fire alarm work and testing completed acceptable. Permit finaled.