BLD13-01935
| FIRE-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 5:11:05 PM | P | PART |
|
|
Final pending paving/site access. Remainder of fire life safety passed.
|
FIR14-00100
| INSP-Sprinkler Rough-in | 2/20/2014 | 2/21/2014 | 2/21/2014 5:08:21 PM | P | PART |
|
|
OH rough-in approved for cover.
|
FIR14-00103
| INSP-Sprinkler Rough-in | 2/21/2014 | 2/21/2014 | 2/21/2014 5:06:41 PM | P | PART |
|
|
UG fire supply line ductile riser and stub to a point 9' beyond the stem wall approved for bury.
|
BLD13-03477
| FIRE-Final Inspection | 2/21/2014 | 2/21/2014 | 2/21/2014 2:01:15 PM | P | PASS |
|
|
Fire life safety passed.
|
FIR14-00048
| INSP-Final Inspection | 2/18/2014 | 2/21/2014 | 2/21/2014 1:11:58 PM | P | FAIL |
|
|
Noted insufficient coverage at four areas, one relocated and three added appliances not shown on plans or included in the calcs, need cd setting adjustment or devices per plan at the boutique. Resubmit plans to match changes and field installation.
|
FIR13-00664
| INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 1:02:57 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD13-02860
| FIRE-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 1:00:47 PM | A | PASS |
|
|
C/N items verified. Fire life safety passed. *Note- fire sprinkler coverage at the shell areas to be maintained at new demising walls as discussed on site.
|
FIR14-00021
| INSP-Final Inspection | 2/21/2014 | 2/21/2014 | 2/21/2014 12:57:55 PM | A | PASS |
|
|
C/N items finished. Fire sprinkler permit finaled.
|
FIR13-00582
| INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 12:55:32 PM | A | PART |
|
|
Blocked upright head at the SW corner, remove foil at uprights, not all areas accessible for inspection due to flooring install underway.
|
FIR13-00706
| INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 11:07:17 AM | A | PART |
|
|
Final pending foam, escutcheon at the cooler dry pendent, field ceiling tile install.
|
FIR14-00079
| INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 11:04:56 AM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions. Permit finaled.
|
FIR14-00066
| INSP-Final Inspection | 2/13/2014 | 2/21/2014 | 2/21/2014 11:03:20 AM | A | PASS |
|
|
Scope of fire alarm work completed and passed functional testing. Permit finaled.
|
FIR11-00228
| INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 9:28:27 AM | A | PASS |
|
|
Remainder of fire alarm work and testing completed acceptable. Permit finaled.
|