Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00262 FIRE-Final Inspection2/21/20172/21/20172/21/2017 1:58:01 PMPPASS
Life safety passed
FIR17-00069 INSP-Final Inspection2/20/20172/21/20172/21/2017 1:18:47 PMPPASS
Permit finaled
BLD16-01779 FIRE-Final Inspection2/21/20172/21/20172/21/2017 1:16:15 PMPPASS
Life safety passed
FIR17-00031 INSP-Final Inspection2/20/20172/21/20172/21/2017 11:03:51 AMAFAIL
New panel tested ok and signals have been verified. Problem is the visual notificaion devices are not sync'd. Provide sync of visual and as-builts showing sync module/changes.
BLD16-04036 FIRE-Final Inspection2/20/20172/21/20172/21/2017 8:55:49 AMAPASS
Life safety passed.
FIR17-00050 INSP-Final Inspection2/21/20172/21/20172/21/2017 8:55:32 AMPPASS
Permit finaled
FIR16-00284 INSP-Sprinkler Rough-in2/20/20172/21/20172/21/2017 8:54:51 AMAPASS
Unit 203 piping in the soffits is ok to cover.
FIR17-00061 INSP-Final Inspection2/17/20172/21/20172/21/2017 8:54:25 AMAFAIL
The audible alarm shall be temporal. When tested the new devices are temporal but atleast one of the existing devices is a solid tone. I went over code requirements for audilble and visual devices.