BLD17-00262
| FIRE-Final Inspection | 2/21/2017 | 2/21/2017 | 2/21/2017 1:58:01 PM | P | PASS |
|
|
Life safety passed
|
FIR17-00069
| INSP-Final Inspection | 2/20/2017 | 2/21/2017 | 2/21/2017 1:18:47 PM | P | PASS |
|
|
Permit finaled
|
BLD16-01779
| FIRE-Final Inspection | 2/21/2017 | 2/21/2017 | 2/21/2017 1:16:15 PM | P | PASS |
|
|
Life safety passed
|
FIR17-00031
| INSP-Final Inspection | 2/20/2017 | 2/21/2017 | 2/21/2017 11:03:51 AM | A | FAIL |
|
|
New panel tested ok and signals have been verified. Problem is the visual notificaion devices are not sync'd. Provide sync of visual and as-builts showing sync module/changes.
|
BLD16-04036
| FIRE-Final Inspection | 2/20/2017 | 2/21/2017 | 2/21/2017 8:55:49 AM | A | PASS |
|
|
Life safety passed.
|
FIR17-00050
| INSP-Final Inspection | 2/21/2017 | 2/21/2017 | 2/21/2017 8:55:32 AM | P | PASS |
|
|
Permit finaled
|
FIR16-00284
| INSP-Sprinkler Rough-in | 2/20/2017 | 2/21/2017 | 2/21/2017 8:54:51 AM | A | PASS |
|
|
Unit 203 piping in the soffits is ok to cover.
|
FIR17-00061
| INSP-Final Inspection | 2/17/2017 | 2/21/2017 | 2/21/2017 8:54:25 AM | A | FAIL |
|
|
The audible alarm shall be temporal. When tested the new devices are temporal but atleast one of the existing devices is a solid tone. I went over code requirements for audilble and visual devices.
|