Inspections for the day of: Tuesday, February 21, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01515 FIRE-Final Inspection2/21/20172/21/20172/21/2017 2:21:03 PMPFAIL
No fire extinguishers mounted in corridors of interior storage units, fire extinguishers need to be mounted per note number 1 of the fire code review comments, a total of 7 need to be installed.
BLD15-01997 FIRE-Final Inspection2/17/20172/21/20172/21/2017 11:07:42 AMAPART
Partial life fire safety inspection complete. Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is in place. There is a building permit for racking associated with this tenant that is not attached to this project (BLD17-00043), this permit is in issued status, the racking permit will need a final inspection performed, when the racking permit inspection is complete and passed BLD15-01997 permit can be finaled for fire life safety. Signage for the FACP room as well as signage for fire sprinkler riser access will be installed, will verify installation of signage during racking permit inspection
FIR17-00007 INSP-Sprinkler Rough-in2/17/20172/21/20172/21/2017 9:27:02 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping located in area of work complete, area of work approved for cover. Noted that the fire sprinkler heads located next to the commercial cooking hood are 155 degree heads, recommend that the heads around the cooking hood be changed to 200 degree heads due to heat from cooking appliances.
BLD15-03172 FIRE-Final Inspection2/17/20172/21/20172/21/2017 8:55:53 AMAFAIL
Round type door handle on north exit door needs to be replaced with single action lever type door hardware. Same northside exit door has wood and bracketing across the door securing the door shut, wood and bracket needs to be removed permenantly for emergency egress at all times. Thumb-turn deadbolt on main front entry needs to be changed to a double-key deadbolt and the proper signage installed on main door as specified in fire code review comments. No fire extingusher on site at time of inspection, fire extinguisher will need to be tagged with the correct inspection tag and mounted before final fire inspection.
FIR17-00055 INSP-Final Inspection2/20/20172/21/20172/21/2017 8:27:15 AMAPASS
Final fire sprinkler inspection passed/complete
FIR17-00062 INSP-Final Inspection2/17/20172/21/20172/21/2017 12:00:00 AMACANC
Patton Phone #: ###-####
FIR16-00299 INSP-Sprinkler Rough-in2/16/20172/21/20172/16/2017 1:58:07 PMACANC
Contact will be Ken Orahood please contact him 30 minutes before Inspection Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank