Inspections for the day of: Wednesday, February 21, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00355 Electrical Rough-In2/21/20182/21/20182/21/2018 2:32:23 PMPPASS
Ceiling grid rough in ok cover
ELE18-00355 Final2/21/20182/21/20182/21/2018 2:31:43 PMPPART
This Should Be Ready By 100 I Left The Ceiling Ooen As Well Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
Products prepared off site. K-8 warmer/cooker 120 volt GFCI in place and K-30 panini grills 2 pole 20 amp only items used for cooking. 2 pole 30 amp for ece maker GFCI required as well.

210.8- GFCI devices shall not be located where not readily accessible. Data GFCI located above 6'7". Due to GE products not available in Boise area any longer 2-pole receptacles to be either GFCI protected or hardwire appliances with disconnecting means. TCO ok
ELE17-04234 Final2/20/20182/21/20182/21/2018 1:38:49 PMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE17-04311 Final2/20/20182/21/20182/21/2018 1:38:24 PMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE17-01967 Final2/20/20182/21/20182/21/2018 12:28:49 PMAPASS
Install 3 park signs.1 at corner of 9th and Front, 1 at corner of 10th and front,1 at entrance into garage on 10th street. Install 2 pay stations sign on North side. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE17-01967 Electrical Rough-In2/20/20182/21/20182/21/2018 12:28:23 PMAPASS
Install 3 park signs.1 at corner of 9th and Front, 1 at corner of 10th and front,1 at entrance into garage on 10th street. Install 2 pay stations sign on North side. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing and disconnecting means confirmed. Final ok
ELE17-03834 Final2/20/20182/21/20182/21/2018 10:52:57 AMAPASS
Requesting Final Inspection for 1st floor. Randy Fox will be on site to assist , if needed. Phone #: ###-#### Inspection requested via web by Kurt Carlson
Final ok
ELE17-01337 Electrical Rough-In2/20/20182/21/20182/21/2018 10:05:01 AMAPASS
We are requesting a wall rough-in inspection for the meeting room outside walls for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Exterior walls only of meeting room and conference room and bathroom wall rough in ok cover
ELE17-03671 Final2/20/20182/21/20182/21/2018 9:33:02 AMAFAIL
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine
Garage door openers not installed yet lift door.
110.3- Devices shall be wired as per instructions. 2 receptacles reverse polarity left of fireplace.
300.15- All boxes shall have covers or canopies. Hook up oven, hood, m vanity lts. 422.30- A disconnecting means shall be provided for all permanently connected appliances. Oven, hood.
ELE17-04155 Final2/20/20182/21/20182/21/2018 8:57:12 AMAPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE17-01563 Final2/20/20182/21/20182/20/2018 2:55:35 PMACANC
Install 1 sign reading "Parking" and 1 sign reading "The Fowler" ,1 round park sign and 1 sidewalk kiosk with parking counter.. ALL PRIMARY POWER BY OTHERS. Phone #: ###-#### >> Inspection requested via web by Ken Olsen Inspection cancelled from web by: Ken Olsen
ELE17-01563 Electrical Rough-In2/20/20182/21/20182/20/2018 2:55:33 PMACANC
Install 1 sign reading "Parking" and 1 sign reading "The Fowler" ,1 round park sign and 1 sidewalk kiosk with parking counter.. ALL PRIMARY POWER BY OTHERS. Phone #: ###-#### >> Inspection requested via web by Ken Olsen Inspection cancelled from web by: Ken Olsen