ELE20-00621
| Final | 2/20/2020 | 2/21/2020 | 2/21/2020 2:55:05 PM | P | PASS |
|
|
Please call Dakota @ ###-#### with any questions. Phone #: ###-#### Inspection requested via web by William Salts Final ok
|
ELE20-00621
| Permanent Service | 2/21/2020 | 2/21/2020 | 2/21/2020 2:33:36 PM | P | PASS |
|
|
Please call Dakota @ ###-#### with any questions. Phone #: ###-#### Inspection requested via web by William Salts p/s u/g rec ok
|
ELE20-00617
| Final | 2/20/2020 | 2/21/2020 | 2/21/2020 2:25:38 PM | P | NR |
|
|
Mark Phone #: ###-#### Needed permanent service inspection.
|
ELE20-00617
| Permanent Service | 2/21/2020 | 2/21/2020 | 2/21/2020 2:19:24 PM | P | PASS |
|
|
Mark Phone #: ###-#### Minimum work space shall be provided as per 110.26. Work bench present in front of panel location. Ground rods shall be flush or recessed in ground as per 250.53(G). About 10" above grade at time of inspection. At time of inspection grounding electrode installed and service entrance conductors being installed. All branch circuits still need to be installed in new main breaker panel. p/s u/g rec ok
|
ELE19-04915
| Final | 2/20/2020 | 2/21/2020 | 2/21/2020 1:32:38 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Approved set of prints on site. Final ok
|
ELE20-00302
| Final | 2/21/2020 | 2/21/2020 | 2/21/2020 12:48:19 PM | A | PASS |
|
|
Please call Bruce @ ###-#### with any questions/concerns
Thank you ; have a lovely weekend! Phone #: ###-#### Inspection requested via web by JENNY EMEL . Approved print on site. Final ok
|
ELE20-00594
| Electrical Rough-In | 2/20/2020 | 2/21/2020 | 2/21/2020 11:54:30 AM | A | PASS |
|
|
Call when you get there 10th floor // Jose Phone #: ###-#### Few luminaires relocated and few receptacles relocated in floor. Rough in ok cover floor and ceiling.
|
ELE19-02646
| Electrical Rough-In | 2/21/2020 | 2/21/2020 | 2/21/2020 11:35:17 AM | A | PASS |
|
|
Requesting 11:00 am inspection. Wall sign install. Phone #: ###-#### Inspection requested via web by Ken Olsen Disconnecting means located in ceiling space where drivers are located, Blade sign yet to install. Rough in ok.
|
ELE19-04444
| Final | 2/20/2020 | 2/21/2020 | 2/21/2020 11:02:28 AM | A | FAIL |
|
|
door code is 1974 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(A)(2)- Receptacle outlets shall be installed with in 6' each side of fireplace wall space. Such receptacles shall not be located in cabinets. 210.52(C)- Pantry counter top shall have receptacle outlets installed so that at no point on counter is more than 24" from a receptacle outlets. 250.94- A intersystem bond bar shall be installed to bond communication systems. 314.21- Drywall shall be repaired around RV receptacle box so gap around box does not exceed 1/8". 406.5(D)- Garage door opener receptacle shall have a cover installed so receptacle is flush with cover plate. 410.16(A)- Luminaires located in master clothes closet shall have totally enclosed lamps.
|
ELE20-00536
| Final | 2/19/2020 | 2/21/2020 | 2/21/2020 10:34:15 AM | A | PASS |
|
|
Service upgrade final Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
|
ELE20-00620
| Temporary Service | 2/20/2020 | 2/21/2020 | 2/21/2020 9:04:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE20-00618
| Temporary Service | 2/20/2020 | 2/21/2020 | 2/21/2020 9:04:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE20-00619
| Temporary Service | 2/20/2020 | 2/21/2020 | 2/21/2020 9:03:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE19-04915
| Final | 2/20/2020 | 2/21/2020 | 2/20/2020 10:36:02 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Steven Ragan Inspection cancelled from web by: Steven Ragan
|