Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03823 ELE-Aging Inspection2/21/20202/21/20202/24/2020 5:15:02 AM DONE
Scheduled for 6/1/20 as per homeowner
ELE20-00394 Conference2/20/20202/21/20202/21/2020 2:15:13 PMPDONE
Robert Phone #: ###-#### Discussed bus rating and labeling. Homeowner has a grasp on what he is doing.
ELE19-00947 Electrical Rough-In2/21/20202/21/20202/21/2020 1:35:28 PMPPASS
Andy Phone #: ###-#### Ok cover 1st floor hardlid up high by N stairwell.
ELE19-03782 Permanent Service2/21/20202/21/20202/21/2020 1:33:28 PMPPASS
Joe Phone #: ###-#### Parallel 3/0's used and landed under lugs rated for 2 each 250kcmil. 2 grd rods. p/s o/h n ok
ELE20-00576 Permanent Service2/20/20202/21/20202/21/2020 12:42:45 PMPCANC
Talked to contractor switched p/s to tomorrow. Wasnt ready. As per contractor.
ELE20-00628 Electrical Rough-In2/21/20202/21/20202/21/2020 12:20:48 PMPPASS
Rough-in kitchen ; laundry. - please go as late in afternoon as possible. Call Kenny ###-#### when on your way. Phone #: ###-#### Inspection requested via web by Kendra Lanham Ok cover ceiling with pendants, and W wall kitchen, S wall laundry.
ELE20-00137 Electrical Rough-In2/20/20202/21/20202/21/2020 12:02:57 PMPPASS
This is a rough-in inspection for solar. We are starting the project tomorrow afternoon and will be finished on Saturday. Please call Logan or Jed if you have any questions. Logan: 208.761.4280 - Jed 801.875.3714 Phone #: ###-#### Inspection requested via web by Bryan Lawley Verified UL listing. Panel model matches paperwork
ELE19-04282 Final2/20/20202/21/20202/21/2020 11:56:25 AMAFAIL
Homeowner will be on site at 830am Phone #: ###-#### Inspection requested via web by Ryan Wilson
1. West side of garage not GFI protected.
2. Recepts under stairs not GFI protected.
3. Connector needed for MC going into heating unit under stairs.
4. Recept front of garage not GFI protected.
5. Island recepts not tamper resistant.
Notice posted on panel cover.
ELE20-00496 Electrical Rough-In2/21/20202/21/20202/21/2020 11:31:59 AMPPASS
We will be onsite with all the equipment starting around 11am Phone #: ###-#### Inspection requested via web by Jesse Simpson Verified UL listing.
ELE19-01808 Final2/20/20202/21/20202/21/2020 11:28:46 AMAPASS
Please call 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by Kenneth Lamm Ok final. 1 piece vanity in place and screwed and caulked to wall. Homeowner had blanked box below vanity. Existing #14 wire went from existing bed outlet to 3 gang for bathroom. Had homeowner cut #14 at entry of 3 gang box with 20a circuit so as it cannot ever be energized
ELE20-00322 Rough-In Permanent Service2/18/20202/21/20202/21/2020 10:31:48 AMAPASS
Please let me know if you have any questions! Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings Ok cover. p/s u/g n ok
ELE19-04524 Final2/20/20202/21/20202/21/2020 10:26:09 AMANR
Front door code 1111 Inspection requested via web by Dan Hobdey Lockout needed for hood. Unable to leave voicemail with ###-####
ELE20-00481 Electrical Rough-In2/20/20202/21/20202/21/2020 9:36:50 AMAPASS
underground inspection requested. Phone #: ###-#### Inspection requested via web by Bayley Beard Ok cover rebar cage. Cage is to be used for support of new awning for grocery pickup. There is no electrical involved with cage.
ELE20-00377 Final2/19/20202/21/20202/21/2020 9:35:40 AMAPASS
Upgraded service panel to new 200 amp all-in-one on back of house. This now feeds original bkr panel in the house and an existing sub panel in the garage (which we pulled a ground into.) Installed 2 new circuits in the garage (120v recep and 240v welding recep) and 3 circuits on the back of the house. All new circuits are from all-in-one meter panel.
Homeowner is Darin Franklin (2087031654), he said he''d be there to show you around. Any questions, of if you want me to meet there just give me 15 min notice, at 2087898804. Thanks ~Dan Phone #: ###-#### Inspection requested via web by Dan Hilke Ok final.
ELE20-00393 Electrical Rough-In2/20/20202/21/20202/21/2020 8:46:08 AMAPASS
street lighting underground to pole light locations Phone #: ###-#### Inspection requested via web by Debby Pierce Ok cover trench for street lights facing Curling Dr. For future street light inspections, Public Works needs to do the inspection as per Tom Marshall-Public Works. Trench is between 30"-36" deep.