FIR02-00016
| INSP-Conference | 2/21/2002 | 2/22/2002 | 2/22/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 02/21/2002 at 11:03:39. Contact: ###-####. r/i inspection - okay to cover and installed per plans 2/22/2002 12:39:19 PM
|
BLD99-03148
| FIRE-Final Inspection | 2/21/2002 | 2/22/2002 | 2/22/2002 12:00:00 AM | A | PASS |
|
|
###-#### brett final occupancy approved per Dave Miller; kitchen exhaust system upgrade has been bonded 2/21/2002 3:41:32 PM
|
FIR01-00435
| INSP-Alarm Testing | 2/21/2002 | 2/22/2002 | 2/22/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 2/21/2002 12:42:12 PM fail; need standpipe control valve supervised; tampers on antifreeze loop not working; all dampers tested and working except exhaust dampers on 4th floor shafts; in duct detectors installed at dampers in sub basement; need copy of record of completion 2/22/2002 2:24:01 PM
|
FIR01-00432
| INSP-Sprinkler Rough-in/Hydro | 2/21/2002 | 2/22/2002 | 2/22/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 02/21/2002 at 14:21:10. Contact: ###-####. r/i okay for revisions to garage; installed per plans 2/22/2002 3:13:38 PM
|
BLD01-03006
| FIRE-Sprinkler Rough-in | 2/22/2002 | 2/22/2002 | 2/22/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 2/22/2002 12:38:07 PM okay to cover; r/i okay
|