Inspections for the day of: Friday, February 22, 2002.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00016 INSP-Conference2/21/20022/22/20022/22/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 02/21/2002 at 11:03:39. Contact: ###-####. r/i inspection - okay to cover and installed per plans 2/22/2002 12:39:19 PM
BLD99-03148 FIRE-Final Inspection2/21/20022/22/20022/22/2002 12:00:00 AMAPASS
###-#### brett final occupancy approved per Dave Miller; kitchen exhaust system upgrade has been bonded 2/21/2002 3:41:32 PM
FIR01-00435 INSP-Alarm Testing2/21/20022/22/20022/22/2002 12:00:00 AMAFAIL
Scheduled by Inspector: 409 On 2/21/2002 12:42:12 PM fail; need standpipe control valve supervised; tampers on antifreeze loop not working; all dampers tested and working except exhaust dampers on 4th floor shafts; in duct detectors installed at dampers in sub basement; need copy of record of completion 2/22/2002 2:24:01 PM
FIR01-00432 INSP-Sprinkler Rough-in/Hydro2/21/20022/22/20022/22/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 02/21/2002 at 14:21:10. Contact: ###-####. r/i okay for revisions to garage; installed per plans 2/22/2002 3:13:38 PM
BLD01-03006 FIRE-Sprinkler Rough-in2/22/20022/22/20022/22/2002 12:00:00 AMPPASS
Added by Inspector: 409 On 2/22/2002 12:38:07 PM okay to cover; r/i okay