Inspections for the day of: Tuesday, February 22, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00407 Rough-In Permanent Service2/18/20052/22/20052/22/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/18/2005 at 12:04:03 PM. Contact: ###-####. ric ok p/s u/g n ok 2/22/2005 8:13:44 AM
ELE05-00518 Electrical Rough-In2/18/20052/22/20052/22/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/18/2005 at 12:33:14 PM. Contact: ###-####. walls only ok to cover 2/22/2005 10:24:29 AM
ELE03-01806 Conference2/18/20052/22/20052/22/2005 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 2/18/2005 at 2:22:00 PM. Contact: ###-####. met with owner and said gas line,phone box and a/c disc need moved in order to set new service panel 2/22/2005 9:33:31 AM
ELE05-00241 Electrical Rough-In2/21/20052/22/20052/22/2005 12:00:00 AMAPASS
Please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters walls only ok to cover 2/22/2005 10:44:09 AM
ELE05-00284 Electrical Rough-In2/21/20052/22/20052/22/2005 12:00:00 AMAPART
Underground insp., please contact Steve, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to cover 4 crossings 2/22/2005 9:02:33 AM
ELE04-02595 Electrical Rough-In2/21/20052/22/20052/22/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/21/2005 at 4:06:28 PM. Contact: ###-####. 2nd floor n 1/2 baths and soffits ok to cover 2/22/2005 8:42:03 AM
ELE05-00555 Temporary Service2/22/20052/22/20052/22/2005 12:00:00 AMPFAIL
Dan; Phone #: ###-#### Internet Inspection Request from: Jan Rice 240.4(D) #12 wire shall be protected by 20A bkr, 406.8(B)(1) 20A recpt shall use weatherproof cover whether or not plugged into. BCC shall use job id sticker. Called and left message, and left red card. 2/22/2005 1:07:30 PM
ELE05-00537 Electrical Rough-In2/22/20052/22/20052/22/2005 12:00:00 AMPPART
Jeff; Phone #: ###-#### Internet Inspection Request from: Jan Rice west 2 offices ok to cover walls only 2/22/2005 12:08:57 PM
ELE05-00542 Temporary Service2/22/20052/22/20052/22/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/22/2005 at 10:45:40 AM. Contact: ###-####. t/s u/g n ok 2/22/2005 4:17:12 PM
ELE05-00543 Temporary Service2/22/20052/22/20052/22/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/22/2005 at 10:46:43 AM. Contact: ###-####. t/s u/g n ok 2/22/2005 2:47:13 PM
ELE05-00562 Rough-In Permanent Service2/22/20052/22/20052/22/2005 12:00:00 AMPFAIL
dan-- ###-#### 314.20 box shall be flush with surface of wood wall, BCC There shall be an approved set of plans on job, Contr shall use job id sticker. Called contr, left message and correction notice 2/22/2005 1:44:22 PM