BLD04-01832
| FIRE-Final Inspection | 2/18/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | A | CANC |
|
|
Fire life safety not required 2/22/2005 9:19:22 AM
|
BLD04-01832
| FIRE-Alarm Testing | 2/18/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | A | CANC |
|
|
Fire life safety sign off not required 2/22/2005 9:18:32 AM
|
BLD04-02362
| FIRE-Final Inspection | 2/18/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | A | PASS |
|
|
Life safety finaled 2/22/2005 12:18:47 PM
|
BLD04-02103
| FIRE-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | A | PASS |
|
|
I signed on the fire sprinkler line on the sign off card. Other signatures already given. 2/22/2005 9:37:46 AM
|
FIR05-00037
| INSP-Sprinkler Rough-in/Hydro | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | CANC |
|
|
Tile workers were installing the floor so there is no access at this time. 2/22/2005 4:03:24 PM
|
FIR04-00608
| INSP-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled 2/22/2005 4:04:36 PM
|
BLD04-01739
| FIRE-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | PASS |
|
|
Life safety finaled 2/22/2005 9:17:42 AM
|
FIR00-00668
| INSP-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 2/22/2005 1:25:09 PM
|
BLD04-02987
| FIRE-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | FAIL |
|
|
scott --call 1st for access ; Phone #: ###-####
Provide permanant address per review notes 4 and 5. Provide fire extinguisher per note 6. Replace painted sprinkler head at the rear door. Provide sticker at the main exit. Provide sprinkler head in the walk in cooler. Sprinkler work will require permit. 2/22/2005 12:17:26 PM
|
BLD04-02803
| FIRE-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | FAIL |
|
|
Mark; Phone #: ###-#### Repair the exit sign/emergency light in the shp at the west exit. Provide four more emergency lights, one in the shop east end, two in show room and one for the basement egress. Provide approved hardware for the office, restroom, east exterior door and the main entrance. Provide sticker at main entrance. Provide fire extinguisher for basement. 2/22/2005 3:20:09 PM
|
MIS05-00019
| FIR-Final | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 2/22/2005 3:04:29 PM
|
FIR04-00666
| INSP-Sprinkler Rough-in/Hydro | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | FAIL |
|
|
Tenting for the second floor needs minor fixing before getting an approval 2/22/2005 3:55:38 PM
|
FIR04-00777
| INSP-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 12:00:00 AM | P | PASS |
|
|
FIre sprinkler finaled
|