Inspections for the day of: Wednesday, February 22, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00344 ELE-Aging Inspection2/22/20062/22/20062/22/2006 3:31:29 PM NR
ELE06-00620 Electrical Rough-In2/22/20062/22/20062/22/2006 3:31:10 PMPNR
Perferably late afternoon. please call my cell phone at ###-#### 30mins to an hour before inspection if possible. Thank you Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
called
ELE06-00619 Electrical Rough-In2/22/20062/22/20062/22/2006 2:29:07 PMPFAIL
Don -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. not made 300.4 nail plates called
ELE05-03936 Final2/22/20062/22/20062/22/2006 1:41:54 PMPPASS
NEEDS FINAL INSPECTION ON BASEMENT REMODEL. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ELE05-03417 Final2/22/20062/22/20062/22/2006 12:56:33 PMPPASS
Scheduled by a contractor via Hello! on 2/22/2006 at 8:08:57 AM. Contact: ###-####. ok
ELE05-04539 Rough-In Permanent Service2/22/20062/22/20062/22/2006 12:27:07 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g N ok
ELE05-04538 Rough-In Permanent Service2/22/20062/22/20062/22/2006 12:26:41 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g N ok
ELE06-00535 Rough-In Permanent Service2/21/20062/22/20062/22/2006 10:53:32 AMAPASS
Please call ahead to schedule as no one is currently at job site.; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton p/s u/g new ok
ELE05-04118 Final2/21/20062/22/20062/22/2006 10:23:18 AMAFAIL
Scheduled by a contractor via Hello! on 2/21/2006 at 4:29:14 PM. Contact: ###-####. cor. called 110.26 needs clearence sub panel in cabinet, 250.148 terminate all equip grds, in disconnects on roof also needs #10 equip grd for 30 amp on roof 250.122, 300.11(B) shall not secure phone to flex cash area314.25 covers for all boxes, 314.23(E) support boxes on roof with only 1 conduit, note all wiring shall be complete high and low voltages also control wiring done on permit #ele06-00570
ELE06-00442 Final2/21/20062/22/20062/22/2006 9:38:37 AMAPASS
call 30 min prior for access; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok
ELE05-02980 Final2/21/20062/22/20062/22/2006 8:57:06 AMACANC
###-#### chuck not ready called contractor needs new permit for tennant space his permit is for shell and core new permit shall be linked to new bld permit for vanila space
ELE05-03691 Final2/21/20062/22/20062/22/2006 8:55:01 AMAPASS
Kevin -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
ELE06-00619 Electrical Rough-In2/21/20062/22/20062/22/2006 8:16:05 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: DONALD CONLEY
cor. met contractor, 300.4 nail plates 11/4" high and low voltage, 230.28 guy kit for mast needs too be higher up, 348.42 shall not bury 90 degree flex fittings