ELE05-00344
| ELE-Aging Inspection | 2/22/2006 | 2/22/2006 | 2/22/2006 3:31:29 PM | | NR |
|
|
|
ELE06-00620
| Electrical Rough-In | 2/22/2006 | 2/22/2006 | 2/22/2006 3:31:10 PM | P | NR |
|
|
Perferably late afternoon. please call my cell phone at ###-#### 30mins to an hour before inspection if possible. Thank you Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher called
|
ELE06-00619
| Electrical Rough-In | 2/22/2006 | 2/22/2006 | 2/22/2006 2:29:07 PM | P | FAIL |
|
|
Don -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. not made 300.4 nail plates called
|
ELE05-03936
| Final | 2/22/2006 | 2/22/2006 | 2/22/2006 1:41:54 PM | P | PASS |
|
|
NEEDS FINAL INSPECTION ON BASEMENT REMODEL. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
|
ELE05-03417
| Final | 2/22/2006 | 2/22/2006 | 2/22/2006 12:56:33 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/22/2006 at 8:08:57 AM. Contact: ###-####. ok
|
ELE05-04539
| Rough-In Permanent Service | 2/22/2006 | 2/22/2006 | 2/22/2006 12:27:07 PM | P | PASS |
|
|
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g N ok
|
ELE05-04538
| Rough-In Permanent Service | 2/22/2006 | 2/22/2006 | 2/22/2006 12:26:41 PM | P | PASS |
|
|
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i p/s u/g N ok
|
ELE06-00535
| Rough-In Permanent Service | 2/21/2006 | 2/22/2006 | 2/22/2006 10:53:32 AM | A | PASS |
|
|
Please call ahead to schedule as no one is currently at job site.; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton p/s u/g new ok
|
ELE05-04118
| Final | 2/21/2006 | 2/22/2006 | 2/22/2006 10:23:18 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/21/2006 at 4:29:14 PM. Contact: ###-####. cor. called 110.26 needs clearence sub panel in cabinet, 250.148 terminate all equip grds, in disconnects on roof also needs #10 equip grd for 30 amp on roof 250.122, 300.11(B) shall not secure phone to flex cash area314.25 covers for all boxes, 314.23(E) support boxes on roof with only 1 conduit, note all wiring shall be complete high and low voltages also control wiring done on permit #ele06-00570
|
ELE06-00442
| Final | 2/21/2006 | 2/22/2006 | 2/22/2006 9:38:37 AM | A | PASS |
|
|
call 30 min prior for access; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok
|
ELE05-02980
| Final | 2/21/2006 | 2/22/2006 | 2/22/2006 8:57:06 AM | A | CANC |
|
|
###-#### chuck not ready called contractor needs new permit for tennant space his permit is for shell and core new permit shall be linked to new bld permit for vanila space
|
ELE05-03691
| Final | 2/21/2006 | 2/22/2006 | 2/22/2006 8:55:01 AM | A | PASS |
|
|
Kevin -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
|
ELE06-00619
| Electrical Rough-In | 2/21/2006 | 2/22/2006 | 2/22/2006 8:16:05 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DONALD CONLEY cor. met contractor, 300.4 nail plates 11/4" high and low voltage, 230.28 guy kit for mast needs too be higher up, 348.42 shall not bury 90 degree flex fittings
|