Inspections for the day of: Wednesday, February 22, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00126 INSP-Sprinkler Rough-in2/22/20062/22/20062/22/2006 4:28:28 PMPPART
UG fire supply line is partially approved for cover. The yard piv, thrust blocks, MJ 90, ductile, tracer wire, and street connections are not completed at this time.
FIR05-00289 INSP-Final Inspection2/21/20062/22/20062/22/2006 4:23:27 PMAPASS
Fire sprinkler permit related work is acceptable, permit finaled.
BLD05-03299 FIRE-Final Inspection2/22/20062/22/20062/22/2006 1:50:53 PMPPASS
c/n items have been completed, life safety is satisfactory.
BLD05-00748 FIRE-Final Inspection2/22/20062/22/20062/22/2006 1:49:44 PMPFAIL
A fire extinguisher has been installed as requested by previous inspection, hardware at the center door must meet requirements of IFC 2003 per plan review notes. Life safety final is acceptable pending resolution of hardware issues at the center door as discussed.
FIR06-00038 INSP-Sprinkler Rough-in/Hydro2/22/20062/22/20062/22/2006 12:39:13 PMPPART
Overhead rough-in at the hard lid area adjacent to the elevator lobby is good for cover.
FIR06-00020 INSP-Final Inspection2/22/20062/22/20062/22/2006 11:51:49 AMPPASS
Fire sprinkler finaled.
BLD05-03230 FIRE-Final Inspection2/21/20062/22/20062/22/2006 11:51:01 AMAPART
Fire life safety is acceptable, final pending signature on occupancy request which was not made available on site as requested and required as a condition of the permit.
FIR05-00616 INSP-Final Inspection2/20/20062/22/20062/22/2006 11:44:36 AMAFAIL
Two storage rooms and one housekeeping room will require smoke detection, relocate one strobe in the staff lounge to provide full coverage, add missing strobe in the locker room, provide visual notification for the work station adjacent to the corridor.