FIR06-00062
| INSP-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 5:02:34 PM | P | CANC |
|
|
Request inspection at approx: 2:00 PM if possible.; Phone #: ###-#### Internet Inspection Request from: Michael Heath
|
FIR05-00768
| INSP-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 5:02:10 PM | P | PASS |
|
|
Permit finaled. Contractor provided verification that the duct smoke detectors mounted in the 90 met the manufactures requirements.
|
FIR06-00009
| INSP-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 2:55:57 PM | A | FAIL |
|
|
Could not give final due to missing ceiling tile and two heads that are still overspaced. Sprinkler piping is ok to cover.
|
FIR06-00018
| INSP-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 12:17:59 PM | A | FAIL |
|
|
Provide 18" separation between the fryer and the grill and move the appliances under the hood to meet 6" minimum. Provide final documents
|
BLD05-03299
| FIRE-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 11:03:35 AM | A | FAIL |
|
|
repair the emergency light in the rear exit corridor and the exit sign/emergency light combo in the pass through near the front of the tenant
|
FIR06-00054
| INSP-Final Inspection | 2/21/2006 | 2/22/2006 | 2/22/2006 9:20:43 AM | A | PASS |
|
|
Sprinkler permit finaled
|