Inspections for the day of: Wednesday, February 22, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00062 INSP-Final Inspection2/21/20062/22/20062/22/2006 5:02:34 PMPCANC
Request inspection at approx: 2:00 PM if possible.; Phone #: ###-#### Internet Inspection Request from: Michael Heath
FIR05-00768 INSP-Final Inspection2/21/20062/22/20062/22/2006 5:02:10 PMPPASS
Permit finaled. Contractor provided verification that the duct smoke detectors mounted in the 90 met the manufactures requirements.
FIR06-00009 INSP-Final Inspection2/21/20062/22/20062/22/2006 2:55:57 PMAFAIL
Could not give final due to missing ceiling tile and two heads that are still overspaced. Sprinkler piping is ok to cover.
FIR06-00018 INSP-Final Inspection2/21/20062/22/20062/22/2006 12:17:59 PMAFAIL
Provide 18" separation between the fryer and the grill and move the appliances under the hood to meet 6" minimum. Provide final documents
BLD05-03299 FIRE-Final Inspection2/21/20062/22/20062/22/2006 11:03:35 AMAFAIL
repair the emergency light in the rear exit corridor and the exit sign/emergency light combo in the pass through near the front of the tenant
FIR06-00054 INSP-Final Inspection2/21/20062/22/20062/22/2006 9:20:43 AMAPASS
Sprinkler permit finaled