Inspections for the day of: Thursday, February 22, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00608 Temporary Service2/22/20072/22/20072/22/2007 3:33:27 PMPCANC
brad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, no transformers to ground to, said he would call later
ELE06-04591 Final2/22/20072/22/20072/22/2007 2:39:04 PMPPASS
ok to final
ELE07-00361 Permanent Service2/22/20072/22/20072/22/2007 2:32:49 PMPPASS
warren - around 2 pm if possible; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s, o/h, rec, ok
ELE07-00604 Rough-In Permanent Service2/22/20072/22/20072/22/2007 2:19:08 PMPCANC
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see ri and p/s
ELE07-00604 Electrical Rough-In2/22/20072/22/20072/22/2007 2:18:32 PMPFAIL
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr, left corr notice, NEC 110.12(C) there shall be no broken parts, 210.52(A)(1) recpt shall be installed so no point is over 6' along floor line from outlet, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member,BCC all u/g shall be inspected before cover
ELE07-00604 Permanent Service2/22/20072/22/20072/22/2007 2:14:50 PMPPASS
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g n ok
ELE07-00589 Final2/22/20072/22/20072/22/2007 1:16:34 PMPPASS
pLEASE INSPECT OUR A/C HOOKUP. THANKS
Phone #: ###-#### x0000 ok to final
ELE07-00599 Electrical Rough-In2/22/20072/22/20072/22/2007 12:36:15 PMPPART
zane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left message, basement area only ok to cover, need to see main and upper floors and pool areas, and subpanel
ELE07-00361 Permanent Service2/21/20072/22/20072/22/2007 10:14:31 AMACANC
warren - late morning; Phone #: ###-#### Internet Inspection Request from: Victoria Beall contr ran into problems, asked to cancel for am, will call for pm
ELE06-04658 Rough-In Permanent Service2/22/20072/22/20072/22/2007 9:48:12 AMAPASS
Scheduled by a contractor via Hello! on 2/22/2007 at 7:26:09 AM. Contact: ###-####. p/s, exst meter pak ,n, ok
ELE07-00593 Temporary Service2/21/20072/22/20072/22/2007 9:22:16 AMAPASS
Bob,
I have two temp poles to inspect. I put the wrong permit number on both of them. The first temp pole should have been
ELE07-00591 and the second one is this one. (Sorry was having a bad blonde day!) Questions call me at ###-####! Yep, it is Kathy from Race. After all these row houses you will know me well!!! Phone #: ###-#### called left message to chg abrasion prot for gec, t/s o/h n ok
ELE07-00591 Temporary Service2/21/20072/22/20072/22/2007 9:21:13 AMAPASS
###-####- luke t/s o/h n ok, called contr left message to chg abrasion protection for gec
ELE07-00155 Conference2/21/20072/22/20072/22/2007 8:51:14 AMADONE
Call before inspection Phone #: ###-#### met owner, contr, 324 and reviewed job, found to be ok unless owner wants to have elect do extra work
ELE06-03404 Electrical Rough-In2/21/20072/22/20072/22/2007 8:01:02 AMAPASS
Ceiling rough-in Phone #: ###-#### ok to cover ceiling only, called contr to post address
ELE07-00592 Temporary Service2/21/20072/22/20072/21/2007 10:08:13 PMACANC
Phone #: ###-#### Inspection cancelled from web by: KATHY WEIL