ELE07-00608
| Temporary Service | 2/22/2007 | 2/22/2007 | 2/22/2007 3:33:27 PM | P | CANC |
|
|
brad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, no transformers to ground to, said he would call later
|
ELE06-04591
| Final | 2/22/2007 | 2/22/2007 | 2/22/2007 2:39:04 PM | P | PASS |
|
|
ok to final
|
ELE07-00361
| Permanent Service | 2/22/2007 | 2/22/2007 | 2/22/2007 2:32:49 PM | P | PASS |
|
|
warren - around 2 pm if possible; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s, o/h, rec, ok
|
ELE07-00604
| Rough-In Permanent Service | 2/22/2007 | 2/22/2007 | 2/22/2007 2:19:08 PM | P | CANC |
|
|
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see ri and p/s
|
ELE07-00604
| Electrical Rough-In | 2/22/2007 | 2/22/2007 | 2/22/2007 2:18:32 PM | P | FAIL |
|
|
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr, left corr notice, NEC 110.12(C) there shall be no broken parts, 210.52(A)(1) recpt shall be installed so no point is over 6' along floor line from outlet, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member,BCC all u/g shall be inspected before cover
|
ELE07-00604
| Permanent Service | 2/22/2007 | 2/22/2007 | 2/22/2007 2:14:50 PM | P | PASS |
|
|
glen - and grounding; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g n ok
|
ELE07-00589
| Final | 2/22/2007 | 2/22/2007 | 2/22/2007 1:16:34 PM | P | PASS |
|
|
pLEASE INSPECT OUR A/C HOOKUP. THANKS Phone #: ###-#### x0000 ok to final
|
ELE07-00599
| Electrical Rough-In | 2/22/2007 | 2/22/2007 | 2/22/2007 12:36:15 PM | P | PART |
|
|
zane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left message, basement area only ok to cover, need to see main and upper floors and pool areas, and subpanel
|
ELE07-00361
| Permanent Service | 2/21/2007 | 2/22/2007 | 2/22/2007 10:14:31 AM | A | CANC |
|
|
warren - late morning; Phone #: ###-#### Internet Inspection Request from: Victoria Beall contr ran into problems, asked to cancel for am, will call for pm
|
ELE06-04658
| Rough-In Permanent Service | 2/22/2007 | 2/22/2007 | 2/22/2007 9:48:12 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/22/2007 at 7:26:09 AM. Contact: ###-####. p/s, exst meter pak ,n, ok
|
ELE07-00593
| Temporary Service | 2/21/2007 | 2/22/2007 | 2/22/2007 9:22:16 AM | A | PASS |
|
|
Bob, I have two temp poles to inspect. I put the wrong permit number on both of them. The first temp pole should have been ELE07-00591 and the second one is this one. (Sorry was having a bad blonde day!) Questions call me at ###-####! Yep, it is Kathy from Race. After all these row houses you will know me well!!! Phone #: ###-#### called left message to chg abrasion prot for gec, t/s o/h n ok
|
ELE07-00591
| Temporary Service | 2/21/2007 | 2/22/2007 | 2/22/2007 9:21:13 AM | A | PASS |
|
|
###-####- luke t/s o/h n ok, called contr left message to chg abrasion protection for gec
|
ELE07-00155
| Conference | 2/21/2007 | 2/22/2007 | 2/22/2007 8:51:14 AM | A | DONE |
|
|
Call before inspection Phone #: ###-#### met owner, contr, 324 and reviewed job, found to be ok unless owner wants to have elect do extra work
|
ELE06-03404
| Electrical Rough-In | 2/21/2007 | 2/22/2007 | 2/22/2007 8:01:02 AM | A | PASS |
|
|
Ceiling rough-in Phone #: ###-#### ok to cover ceiling only, called contr to post address
|
ELE07-00592
| Temporary Service | 2/21/2007 | 2/22/2007 | 2/21/2007 10:08:13 PM | A | CANC |
|
|
Phone #: ###-#### Inspection cancelled from web by: KATHY WEIL
|