ELE08-00100
| Electrical Rough-In | 2/22/2008 | 2/22/2008 | 2/22/2008 4:50:50 PM | P | PART |
|
|
Call Chad early for access. Phone #: ###-#### Internet Inspection Request from: Todd Sellman walls in new lobby and conference rms, and u/g
|
ELE08-00338
| Electrical Rough-In | 2/22/2008 | 2/22/2008 | 2/22/2008 4:07:06 PM | P | PART |
|
|
jim - grounding Phone #: ###-#### ok for concrete and dirt
|
ELE08-00426
| Permanent Service | 2/22/2008 | 2/22/2008 | 2/22/2008 3:33:12 PM | P | PASS |
|
|
p/s u/g rec. ok still needs final for grd or bond to water #4 copper
|
ELE08-00433
| Electrical Rough-In | 2/21/2008 | 2/22/2008 | 2/22/2008 3:06:15 PM | P | PART |
|
|
TOBY Phone #: ###-#### Internet Inspection Request from: Sean DeLacy patio deck wiring ok
|
ELE08-00432
| Electrical Rough-In | 2/21/2008 | 2/22/2008 | 2/22/2008 3:05:50 PM | P | PART |
|
|
TOBY Phone #: ###-#### Internet Inspection Request from: Sean DeLacy patio deck wiring ok
|
ELE08-00175
| Permanent Service | 2/22/2008 | 2/22/2008 | 2/22/2008 2:24:49 PM | P | PASS |
|
|
tim Phone #: ###-#### p/s u/g ok for meter
|
ELE08-00047
| Final | 2/22/2008 | 2/22/2008 | 2/22/2008 1:22:53 PM | P | FAIL |
|
|
Alan Phone #: ###-#### corr met contr.xray equipment shall be wired to meet 517.71,517.78(C) and 517.13(A&B)
|
ELE08-00431
| Temporary Service | 2/22/2008 | 2/22/2008 | 2/22/2008 12:37:31 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/22/2008 at 10:18:47 AM. t/s u/g new ok
|
ELE08-00438
| Temporary Service | 2/21/2008 | 2/22/2008 | 2/22/2008 11:40:28 AM | P | PASS |
|
|
James ###-#### T/S O/H Ok
|
ELE07-02064
| Electrical Rough-In | 2/21/2008 | 2/22/2008 | 2/22/2008 11:01:53 AM | A | PART |
|
|
Jared-ceiling cover please Phone #: ###-#### ceilings anop
|
ELE08-00431
| Temporary Service | 2/21/2008 | 2/22/2008 | 2/22/2008 10:07:51 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/21/2008 at 12:00:53 PM. Contact: ###-####. met with contractor explained what is required for all temp services and wiring to job shacks
|
ELE08-00047
| Final | 2/21/2008 | 2/22/2008 | 2/22/2008 9:31:06 AM | A | NH |
|
|
alan Phone #: ###-#### notice posted
|
ELE08-00199
| Permanent Service | 2/22/2008 | 2/22/2008 | 2/22/2008 9:25:09 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/22/2008 at 6:37:45 AM. Contact: ###-####. needs new permit for new service called also move phone and catv for clearence, and install equip grd in nipple to 200 amp subpanel note service is on garage, and garage is not allowed per BLD 07-01319 it states seperate permit required for garage
|