Inspections for the day of: Wednesday, February 22, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00021 FIR-Aging Inspection2/22/20122/22/20122/23/2012 10:56:44 AM NR
Mary with Taylor brothers is following up on this project and all other General fire outstanding permits.
FIR06-00015 FIR-Aging Inspection2/22/20122/22/20122/23/2012 10:53:11 AM NR
Mary with Taylor brothers is following up on this project and all other General fire outstanding permits.
FIR06-00062 FIR-Aging Inspection2/22/20122/22/20122/23/2012 10:52:20 AM NR
Mary with Taylor brothers is following up on this project and all other General fire outstanding permits.
BLD11-02923 FIRE-Final Inspection2/22/20122/22/20122/22/2012 3:40:52 PMPPASS
Life safety passed.
FIR12-00054 INSP-Sprinkler Rough-in2/22/20122/22/20122/22/2012 3:39:06 PMPPASS
Todays inspection covered the hangers and their attachment to the building structure. The fitter wants to use fencing nails to hold the all thread rods to the trusses thus elliminating the branchline seismic bracing. I defered him to plan review for a determination.
BLD11-02932 FIRE-Conference2/22/20122/22/20122/22/2012 2:46:26 PMPDONE
Conference for emergency lights. I was ok with deleting the emergency light in the center of the seating area since there will be lights at both the front and rear exit doors in the seating area.
BLD11-01685 FIRE-Conference2/21/20122/22/20122/22/2012 12:36:07 PMADONE
JIm Greenwood and I went over the outside alarm bell placement. We also discussed how the bell was activated and wiring layout. We also discussed mag locks on the main exit and I deferred him to plan review for answers since this since access/egress control issues were not addressed on the plans.
BLD11-02923 FIRE-Final Inspection2/21/20122/22/20122/22/2012 11:38:36 AMAFAIL
Provide occupant load sign and annual inspection for the fire extinguishers.
FIR11-00631 INSP-Sprinkler Rough-in2/21/20122/22/20122/22/2012 11:37:42 AMAPASS
24 hour air test passed
BLD11-02505 FIRE-Final Inspection2/21/20122/22/20122/22/2012 8:04:12 AMAPASS
life safety passed