BLD19-00523
| FIRE-Final Inspection | 2/22/2019 | 2/22/2019 | 2/22/2019 1:48:22 PM | P | FAIL |
|
|
Provide sprinkler modifications, repair or remove the exit signs, provide sticker at the main exit, remove the thumbturn deadbolt at the rear exit
Ryan Phone #: ###-####
|
BLD18-03923
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 12:48:12 PM | A | PART |
|
|
Temp for life safety on 3rd floor. Contractor had to remove the new LED bulbs from the emergency lights and re-install the old bulbs for them to work on battery back up. // Steve Phone #: ###-####
|
FIR19-00061
| INSP-Sprinkler Rough-in | 2/22/2019 | 2/22/2019 | 2/22/2019 11:05:36 AM | P | FAIL |
|
|
Could not perform inspection due to the fire sprinkler contractor not submitting plan modifications for approval yet. I did perform a conference with the builder about what could be covered and what could not. We also discussed obstructions caused by lights and the placement of smoke alarms. Call ahead 20 minute - partial // Andy Phone #: ###-####
|
FIR18-00740
| INSP-Alarm Testing | 2/21/2019 | 2/22/2019 | 2/22/2019 11:00:46 AM | A | FAIL |
|
|
I was only able to check the sync of the devices today due to multiple a/v's that are overspaced. Plan modifications are required showing all of the changes required today and all of the changes that have been made on prior inspections. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
BLD19-00454
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 9:05:13 AM | A | PASS |
|
|
Life safety passed
Brady Phone #: ###-####
|
BLD19-00453
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 9:04:50 AM | A | PASS |
|
|
Life safety passed. Brady Phone #: ###-####
|