FIR18-00267
| INSP-Sprinkler Rough-in/Hydro | 2/22/2019 | 2/22/2019 | 2/22/2019 3:39:32 PM | P | PART |
|
|
Hydrostatic test for overhead fire sprinkler piping on level 2 witnessed, no pressure loss observed.
|
FIR19-00108
| INSP-Sprinkler Rough-in | 2/21/2019 | 2/22/2019 | 2/22/2019 3:38:12 PM | P | PART |
|
|
Rough in inspection for overhead fire sprinkler piping in area of work complete. Hydrostatic test to be completed at a later date.
Tom Phone #: ###-####
|
FIR18-00616
| INSP-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 3:37:14 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Please call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-01031
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 12:29:35 PM | A | FAIL |
|
|
FIR permit for associated fire alarm modifications has not been completed and finaled, FIR permit for fire alarms needs to be finaled before life fire safety can be completed.
Stan Phone #: ###-####
|
FIR18-00267
| INSP-Sprinkler Rough-in | 2/21/2019 | 2/22/2019 | 2/22/2019 10:36:32 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping on level 2 complete, notated city approved drawings with red in areas approved for cover.
Justin Phone #: ###-####
|
FIR18-00758
| INSP-Sprinkler Rough-in | 2/22/2019 | 2/22/2019 | 2/22/2019 9:35:32 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work complete, hardlids approved for cover. As-builts will need to be submitted and approved before next inspection.
cordinate inspection with Don Forrester Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
BLD18-01766
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 9:06:08 AM | A | FAIL |
|
|
Attempted to call point of contact at 8:35 AM, left a message to please call me back before 9AM, tried calling again at 8:55AM with no answer, proceeded to next inspection, this request will need to be rescheduled.
Chris Phone #: ###-####
|
BLD18-04300
| FIRE-Final Inspection | 2/22/2019 | 2/22/2019 | 2/22/2019 8:28:43 AM | P | PART |
|
|
Fire sprinkler inspection is complete, fire alarm permit will be in issued status until volume issue is resolved (reference noted under FIR18-00966), 30 day TCO authorized per conversation with Ron Johnson contigent on audio issue on fire alarms getting resolved.
Tom Phone #: ###-####
|
BLD17-01000
| FIRE-Final Inspection | 2/21/2019 | 2/22/2019 | 2/22/2019 8:25:45 AM | A | PART |
|
|
TCO Phase 1 life fire safety inspection complete.
Bruce Phone #: ###-####
|
FIR18-00966
| INSP-Final Inspection | 2/20/2019 | 2/22/2019 | 2/22/2019 8:24:58 AM | A | PART |
|
|
Speaker strobe in elevator lobby is operational, sound on floor still needs to be improved. Per conversation with Ron Johnson a 30 day TCO is authorized pending the audio issue is resolved.
Need to schedule for 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|