Inspections for the day of: Friday, February 22, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00791 Final2/22/20192/22/20192/22/2019 3:16:57 PMPPASS
installer jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC19-00760 Final2/21/20192/22/20192/22/2019 2:33:05 PMPFAIL
Please call on way: Maddie ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- line set needs insulation finished at A/C and penetration sealed
- txv at indoor coil needs insulated
- condensate line for 90% was ran outside and didnt have proper slope. run condensate line to indoor location to prevent freezing
MEC19-00760 Pressure Test2/21/20192/22/20192/22/2019 2:30:24 PMPPASS
Please call on way: Maddie ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- 5lb flue pressure test ok
MEC18-00564 Final2/22/20192/22/20192/22/2019 2:14:19 PMPPASS
Retro final - Witness flue press Phone #: ###-#### Inspection requested via web by Konrad Swartz
- 5lb flue pressure test ok
final ok
MEC19-00545 Rough-in2/22/20192/22/20192/22/2019 2:09:12 PMPPASS
Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- R/I ok
MEC18-03185 Final2/20/20192/22/20192/22/2019 2:03:23 PMPFAIL
Inspection requested via web by Marisa Hone
- A/C has a 30 amp breaker that needs to be a 25 amp
MEC19-00750 Final2/21/20192/22/20192/22/2019 11:15:22 AMAPASS
Please call Home owner with 15 min call ahead. Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- exhaust fan ok
MEC19-00631 Final2/19/20192/22/20192/22/2019 10:01:23 AMAPASS
Please inspect as early as possible. He would like to be the 1st one of day. Does need to be done by 11 AM. Craig Leymaster ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00785 Rough-in2/21/20192/22/20192/22/2019 9:28:30 AMAFAIL
partial inspection Phone #: ###-#### Inspection requested via web by Oleg Chervak
- one dryer vent on 2nd floor SE side was disconnected
- all dryer vents in attic need more support
- I rescheduled this inspection for Monty on monday morning
MEC18-05031 Final2/21/20192/22/20192/22/2019 8:38:27 AMAPASS
GARAGE KEYCODE- 1234 . READY FOR FINAL INSPECTION- IF THERE IS ANY ISSUES ACCESSING PLEASE CALL ANTHONY BOYD-- PROJECT MANAGER.

IF THIS REQUEST IS UNACCEPTABLE SINCE NO ONE THERE PLEASE CALL ME STEVE AT ###-####, WITH DIAMOND HEATING Phone #: ###-#### Inspection requested via web by Rick Montgomery
- mini split final on new shop ok