ELE97-04227
| INSP - Electrical Rough-In | 2/18/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | A | PASS |
|
|
02/23/98 403 - PERM SERV--###-####
|
ELE98-00547
| INSP - Electrical Rough-In | 2/20/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | A | CANC |
|
|
02/22/98 403 - ###-#### steve CONTRACTORS REQUEST. WILL RESCHEDULE.
|
ELE97-04227
| INSP - Electrical Rough-In | 2/23/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | P | PASS |
|
|
02/23/98 403 - R/I WALLS ON 2ND FLOOR--JESSICA ###-####
|
ELE97-04384
| INSP - Final | 2/20/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | P | FAIL |
|
|
02/23/98 403 - doherty elec ###-#### at 3:30 TABLE C1A. 3/0 CABLE IN 2IN. EMT CONDUIT--5 ea. ALLOWED, (CONDUIT TO FULL). 110-3. USE OF EQUIPTMENT. STRANDED WIRE WRAPED AROUND SCREW TERMINAL, (NOT ALLOWED PER JSCHMER.).
|
ELE98-00176
| INSP - Final | 2/23/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | P | PASS |
|
|
02/23/98 403 - BELCHER BLDG--NANCY ###-####
|
ELE98-00250
| INSP - Final | 2/23/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | P | PASS |
|
|
final/remodel office , add office in carpenter shop/###-####
|
ELE98-00457
| INSP - Electrical Rough-In | 2/23/1998 | 2/23/1998 | 2/23/1998 12:00:00 AM | P | PASS |
|
|
02/23/98 403 - ###-#### CESAR CORRECTIONS COMPLETED.
|