Inspections for the day of: Monday, February 23, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00783 INSP-Final Inspection2/20/20042/23/20042/23/2004 12:00:00 AMAFAIL
need horn in place of strobe per plan review notes; 17 amp hr batteries installed in place of 18 amp hr as shown on plans - exceeds requirements for 60 hr; zones changed per one-line: zone 1 is smoke and water flow changed and will be reflected on zone map when provided; knox box needed 2/23/2004 9:09:25 AM
BLD03-00689 FIRE-Conference2/20/20042/23/20042/23/2004 12:00:00 AMAPART
met with GC and other inspectors about requirements for temp occupancy as the SE area of the TI work won't be ready for the final occupancy; sprinklers/alarms must be complete for final and other life safety items 2/23/2004 10:37:45 AM
BLD03-02811 FIRE-Sprinkler Rough-in2/23/20042/23/20042/23/2004 12:00:00 AMPPART
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover hard lids on first floor restroom; need resubmittals per plan review notes 2/23/2004 1:41:43 PM
FIR03-00781 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPPASS
mick ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00153 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:06:48 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:04 PM
FIR03-00154 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:07:31 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:23 PM
FIR03-00155 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:01 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:40 PM
FIR03-00156 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:29 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:57:02 PM
FIR03-00157 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:59 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:57:21 PM
FIR03-00158 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:09:28 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:55:47 PM
FIR03-00159 INSP-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/23/2004 at 11:10:03 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:55:20 PM
FIR03-00784 INSP-Sprinkler Rough-in2/23/20042/23/20042/23/2004 12:00:00 AMPPART
okay to cover hard lid areas in restrooms on first floor; need resubmittals per plan review notes; the 1.5 inch branch line has shifted and the main feed from risers has changed; need strap attached to beam on first floor; second floor not installed yet 2/23/2004 1:41:07 PM
BLD03-02905 FIRE-Final Inspection2/23/20042/23/20042/23/2004 12:00:00 AMPPASS
signed the inspection record for final 2/23/2004 4:34:36 PM