FIR03-00783
| INSP-Final Inspection | 2/20/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | A | FAIL |
|
|
need horn in place of strobe per plan review notes; 17 amp hr batteries installed in place of 18 amp hr as shown on plans - exceeds requirements for 60 hr; zones changed per one-line: zone 1 is smoke and water flow changed and will be reflected on zone map when provided; knox box needed 2/23/2004 9:09:25 AM
|
BLD03-00689
| FIRE-Conference | 2/20/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | A | PART |
|
|
met with GC and other inspectors about requirements for temp occupancy as the SE area of the TI work won't be ready for the final occupancy; sprinklers/alarms must be complete for final and other life safety items 2/23/2004 10:37:45 AM
|
BLD03-02811
| FIRE-Sprinkler Rough-in | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | PART |
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover hard lids on first floor restroom; need resubmittals per plan review notes 2/23/2004 1:41:43 PM
|
FIR03-00781
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | PASS |
|
|
mick ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR03-00153
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:06:48 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:04 PM
|
FIR03-00154
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:07:31 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:23 PM
|
FIR03-00155
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:01 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:40 PM
|
FIR03-00156
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:29 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:57:02 PM
|
FIR03-00157
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:08:59 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:57:21 PM
|
FIR03-00158
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:09:28 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:55:47 PM
|
FIR03-00159
| INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:10:03 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:55:20 PM
|
FIR03-00784
| INSP-Sprinkler Rough-in | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | PART |
|
|
okay to cover hard lid areas in restrooms on first floor; need resubmittals per plan review notes; the 1.5 inch branch line has shifted and the main feed from risers has changed; need strap attached to beam on first floor; second floor not installed yet 2/23/2004 1:41:07 PM
|
BLD03-02905
| FIRE-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 12:00:00 AM | P | PASS |
|
|
signed the inspection record for final 2/23/2004 4:34:36 PM
|