Inspections for the day of: Wednesday, February 23, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00551 Rough-In Permanent Service2/23/20052/23/20052/23/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn ric ok p/s u/g n ok 2/23/2005 9:07:19 AM
ELE05-00199 Final2/23/20052/23/20052/23/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called contr about trim on stair lite, ok to final 2/23/2005 7:59:16 AM
ELE05-00198 Final2/23/20052/23/20052/23/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ok to final 2/23/2005 8:38:41 AM
ELE05-00201 Final2/23/20052/23/20052/23/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ok to final 2/23/2005 8:20:29 AM
ELE04-03954 Final2/23/20052/23/20052/23/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/23/2005 at 7:10:03 AM. Contact: ###-####. called contractor to fix drywall by garage door sw. ok to final 2/23/2005 9:21:10 AM
ELE05-00422 Electrical Rough-In2/23/20052/23/20052/23/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/23/2005 at 7:11:41 AM. Contact: ###-####. 314.17(A) cable clamp shall be provided where cables enter 1/2" ko at garage lites, 314.20 boxes shall be flush with finished surface at garage lites, BCC there shall be an approved set of plans on the job 2/23/2005 9:44:34 AM
ELE05-00382 Final2/22/20052/23/20052/23/2005 12:00:00 AMANR
Scheduled by a contractor via Hello! on 2/22/2005 at 2:16:45 PM. Contact: ###-####. 330.30(B) mc cable shall be supported within 12" of boxes, 358.26 emt shall not have over 360 degree bends, 440.14 disconnects shall be lockable if on panel, 408.4 circuit directory shall be provided. when call again, all recpts to be made-up if want final. 2/23/2005 10:38:11 AM
ELE04-04114 Final2/22/20052/23/20052/23/2005 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 2/22/2005 at 4:14:38 PM. Contact: ###-####. sign not there, gave t/o, 210.8(B)(2) rooftop rcpt shall be gfci, and bathrooms, 110.26(A)(1) disconnect shall have 3' work clearance 2/23/2005 12:48:59 PM 2/23/2005 12:50:10 PM
ELE05-00560 Electrical Rough-In2/23/20052/23/20052/23/2005 12:00:00 AMPPASS
doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore bathroom only ric ok. Need to watch rest of building to see if they are following plans. Changing ceiling grids, but no seismic wires, grid wires too small, recepts being re-installed after panelling taken down. 2/23/2005 1:46:08 PM
ELE05-00555 Temporary Service2/23/20052/23/20052/23/2005 12:00:00 AMPPASS
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok , corrections made 2/23/2005 3:13:55 PM
ELE05-00517 Permanent Service2/23/20052/23/20052/23/2005 12:00:00 AMPPASS
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h reconnect ok, talked to contr and he is going to change out panel inside next week. I told him he needed to strap riser and provide schedule which will be done when he comes back. 2/23/2005 2:13:36 PM
ELE05-00574 Permanent Service2/23/20052/23/20052/23/2005 12:00:00 AMPPASS
duane ###-#### p/s o/h reconnect ok 2/23/2005 1:05:10 PM
ELE05-00562 Electrical Rough-In2/23/20052/23/20052/23/2005 12:00:00 AMPPASS
Dan; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made, ric ok , p/s u/g n ok 2/23/2005 4:41:36 PM