Inspections for the day of: Thursday, February 23, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04467 Permanent Service2/23/20062/23/20062/23/2006 4:07:37 PMPNR
Inspection for perm service. Meter can on pole. Please inspect after 2:00pm and before 3:30pm if possible. IDPCO can re-connect at about 4-4:30pm. Please call if any schedule issues.; Phone #: ###-#### Internet Inspection Request from: todd hall contr way behind and told him to re-call for inspection
ELE06-00633 Temporary Service2/23/20062/23/20062/23/2006 3:58:27 PMPCANC
paul; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met elect, he asked to postpone inspection
ELE06-00194 Final2/23/20062/23/20062/23/2006 3:56:56 PMPPASS
James; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong signed occ card, ok to final
ELE06-00632 Temporary Service2/23/20062/23/20062/23/2006 2:51:48 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g n ok
ELE06-00648 Temporary Service2/23/20062/23/20062/23/2006 1:11:07 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice, 250.24(A) gec shall be connected to grounded conductor bus or terminal, 250.24(B) main bonding jumper shall be connected to grounded conductor
ELE06-00647 Temporary Service2/23/20062/23/20062/23/2006 1:08:50 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice, 250.24(A) gec shall be connected to grounded conductor term or bus,250.24(B) main bonding jumper shall be connected to grounded conductor
ELE06-00482 Electrical Rough-In2/23/20062/23/20062/23/2006 12:29:33 PMPPASS
soffit inspection//danny; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa soffits only ok to cover
ELE06-00646 Temporary Service2/23/20062/23/20062/23/2006 12:18:02 PMPPASS
Internet Inspection Request from: Cevyn Recla t/s u/g n ok
ELE06-00174 Final2/22/20062/23/20062/23/2006 10:14:31 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton signed occ card, ok to final
ELE06-00140 Final2/22/20062/23/20062/23/2006 10:11:53 AMAPASS
Scheduled by a contractor via Hello! on 2/22/2006 at 1:41:23 PM. Contact: ###-#### ok to final, signed card
ELE06-00139 Final2/22/20062/23/20062/23/2006 10:11:09 AMAPASS
Scheduled by a contractor via Hello! on 2/22/2006 at 1:40:19 PM. Contact: ###-####. ok to final, signed card
ELE06-00633 Temporary Service2/22/20062/23/20062/23/2006 10:07:07 AMACANC
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, nr
ELE06-00632 Temporary Service2/22/20062/23/20062/23/2006 10:06:39 AMACANC
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, nr
ELE03-04124 Electrical Rough-In2/22/20062/23/20062/23/2006 9:31:47 AMAFAIL
Jeff -- for cover; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong met owner, left correction notice, 210.52 recpt shall be within 6' of door, 334.80 nm cable shall be secured within 12" of boxes, 250.80 metal enclosures shall be grounded,BCC all make-up shall be done
ELE06-00631 Rough-In Permanent Service2/22/20062/23/20062/23/2006 8:05:51 AMAPASS
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric ok, p/s u/g n ok
ELE04-03805 Final2/23/20062/23/20062/23/2006 12:00:00 AMPPASS
looked at sign, ok to final