BLD05-03401
| FIRE-Final Inspection | 2/21/2006 | 2/23/2006 | 2/24/2006 12:13:39 PM | A | PART |
|
|
Fire life safety for the 1400ft/2 vending/break room and the 340ft/2 smoking break room portion of this permit is satisfactory, the remainder of area under this permit scope is not complete, inspected or approved at this time.
|
FIR05-00616
| INSP-Final Inspection | 2/23/2006 | 2/23/2006 | 2/23/2006 5:06:17 PM | P | PASS |
|
|
Fire alarm finaled.
|
BLD06-00053
| FIRE-Final Inspection | 2/23/2006 | 2/23/2006 | 2/23/2006 3:33:15 PM | P | PASS |
|
|
Life safety is acceptable.
|
BLD06-00054
| FIRE-Final Inspection | 2/23/2006 | 2/23/2006 | 2/23/2006 3:31:56 PM | P | PASS |
|
|
Life safety passed inspection.
|
FIR05-00616
| INSP-Alarm Testing | 2/22/2006 | 2/23/2006 | 2/23/2006 2:31:49 PM | A | PASS |
|
|
c/n items have been completed as requested, changes are indicated on as-built drawings.
|
FIR05-00865
| INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 1:12:06 PM | A | PART |
|
|
Audio/visual and duct detection devices tested satisfactory for the vending/break room and the smoking break room only for a portion of this permit.
|
FIR05-00864
| INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 1:07:03 PM | A | PART |
|
|
Overhead fire sprinkler is complete and the installation is satisfactory at the 1400 ft/2 vending/break room and the 340 ft/2 smoking break room portion of this permit.
|
BLD05-02620
| FIRE-Final Inspection | 2/22/2006 | 2/23/2006 | 2/23/2006 1:01:29 PM | A | CANC |
|
|
Life safety cannot be finaled until the project related fire alarm and sprinkler permits have been inspected and approved.
|
FIR05-00611
| INSP-Final Inspection | 2/22/2006 | 2/23/2006 | 2/23/2006 12:57:46 PM | A | CANC |
|
|
Cancel inspection due to pipe hanger issues as discussed on site.
|
FIR05-00610
| INSP-Final Inspection | 2/22/2006 | 2/23/2006 | 2/23/2006 12:55:08 PM | A | CANC |
|
|
Cancel inspection due to project related sprinkler issues as discussed on site.
|
BLD05-03251
| FIRE-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 12:52:07 PM | A | FAIL |
|
|
The project related fire alarm and sprinkler permits must pass inspection prior to final approval of life safety.
|
FIR05-00807
| INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 12:49:57 PM | A | FAIL |
|
|
Need to reprogram existing under floor detectors for door release at the new roll-up fire door as discussed.
|
FIR05-00811
| INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 12:46:27 PM | A | FAIL |
|
|
One head has not been installed, the field installation does not match approved plans, will require resubmittal reflecting changes.
|