Inspections for the day of: Thursday, February 23, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-03401 FIRE-Final Inspection2/21/20062/23/20062/24/2006 12:13:39 PMAPART
Fire life safety for the 1400ft/2 vending/break room and the 340ft/2 smoking break room portion of this permit is satisfactory, the remainder of area under this permit scope is not complete, inspected or approved at this time.
FIR05-00616 INSP-Final Inspection2/23/20062/23/20062/23/2006 5:06:17 PMPPASS
Fire alarm finaled.
BLD06-00053 FIRE-Final Inspection2/23/20062/23/20062/23/2006 3:33:15 PMPPASS
Life safety is acceptable.
BLD06-00054 FIRE-Final Inspection2/23/20062/23/20062/23/2006 3:31:56 PMPPASS
Life safety passed inspection.
FIR05-00616 INSP-Alarm Testing2/22/20062/23/20062/23/2006 2:31:49 PMAPASS
c/n items have been completed as requested, changes are indicated on as-built drawings.
FIR05-00865 INSP-Final Inspection2/21/20062/23/20062/23/2006 1:12:06 PMAPART
Audio/visual and duct detection devices tested satisfactory for the vending/break room and the smoking break room only for a portion of this permit.
FIR05-00864 INSP-Final Inspection2/21/20062/23/20062/23/2006 1:07:03 PMAPART
Overhead fire sprinkler is complete and the installation is satisfactory at the 1400 ft/2 vending/break room and the 340 ft/2 smoking break room portion of this permit.
BLD05-02620 FIRE-Final Inspection2/22/20062/23/20062/23/2006 1:01:29 PMACANC
Life safety cannot be finaled until the project related fire alarm and sprinkler permits have been inspected and approved.
FIR05-00611 INSP-Final Inspection2/22/20062/23/20062/23/2006 12:57:46 PMACANC
Cancel inspection due to pipe hanger issues as discussed on site.
FIR05-00610 INSP-Final Inspection2/22/20062/23/20062/23/2006 12:55:08 PMACANC
Cancel inspection due to project related sprinkler issues as discussed on site.
BLD05-03251 FIRE-Final Inspection2/21/20062/23/20062/23/2006 12:52:07 PMAFAIL
The project related fire alarm and sprinkler permits must pass inspection prior to final approval of life safety.
FIR05-00807 INSP-Final Inspection2/21/20062/23/20062/23/2006 12:49:57 PMAFAIL
Need to reprogram existing under floor detectors for door release at the new roll-up fire door as discussed.
FIR05-00811 INSP-Final Inspection2/21/20062/23/20062/23/2006 12:46:27 PMAFAIL
One head has not been installed, the field installation does not match approved plans, will require resubmittal reflecting changes.