Inspections for the day of: Friday, February 23, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00459 Electrical Rough-In2/23/20072/23/20072/26/2007 7:52:04 AMPPASS
###-#### Jason walls only ok to cover, called elect to fix cord out back somebody installed, fix mc supports, install locknuts in 8" j-box
ELE07-00615 Permanent Service2/23/20072/23/20072/23/2007 4:42:56 PMPPASS
p/s, o/h, rec, ok, need to check span clearance over shop at final
ELE07-00615 Electrical Rough-In2/22/20072/23/20072/23/2007 4:41:02 PMPPASS
Phone #: ###-#### u/g only ok to cover
ELE07-00620 Conference2/23/20072/23/20072/23/2007 2:58:51 PMPCANC
Brad; Phone #: ###-####, call 1st for access Internet Inspection Request from: Cathy Weisshaupt see ri, wrong type request,
ELE07-00611 Electrical Rough-In2/22/20072/23/20072/23/2007 2:57:21 PMPFAIL
Please call John Phone #: ###-#### called contr, left corr notice, 300.4(A) & (D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal boxes shall be grounded, 314.17(C) nm cable shall be srecured within 8" of box, BCC no violations shall be retained- splices shall be accessible and in box
ELE07-00620 Electrical Rough-In2/23/20072/23/20072/23/2007 12:57:24 PMPFAIL
Brad; Phone #: ###-####, call 1st for access Internet Inspection Request from: Cathy Weisshaupt called, left message, nec 300.4(D) edge of mc cable shall be 1 1/4" from edge of framing member, no mc in valley of 2x4 stud
ELE06-03257 Final2/23/20072/23/20072/23/2007 12:35:41 PMPPASS
hz; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-02438 Final2/22/20072/23/20072/23/2007 10:24:21 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed occ card
ELE07-00571 Permanent Service2/22/20072/23/20072/23/2007 9:26:12 AMAPASS
Partial inspection for final approval. Phone #: ###-#### ok to final, p/s done prior
ELE06-04278 Final2/22/20072/23/20072/23/2007 8:57:56 AMAPASS
PLEASE INSPECT FOR FINAL Phone #: ###-#### x0000 ok to final
ELE07-00554 Final2/22/20072/23/20072/23/2007 8:30:44 AMAPASS
Phone #: ###-#### corr made, ok to final
ELE07-00553 Final2/22/20072/23/20072/23/2007 8:30:10 AMAPASS
Phone #: ###-#### corr made, ok to final
ELE07-00556 Final2/22/20072/23/20072/23/2007 8:29:33 AMAPASS
Phone #: ###-#### corr made, ok to final
ELE07-00014 Final2/22/20072/23/20072/23/2007 8:28:53 AMAPASS
Phone #: ###-#### corr made, ok to final
ELE07-00555 Final2/22/20072/23/20072/23/2007 8:28:12 AMAPASS
Phone #: ###-#### corr made, ok to final
ELE07-00356 Final2/22/20072/23/20072/23/2007 8:04:23 AMAPASS
Phone #: ###-#### ok to cover clg, permits fixed, ok to final, no card to sign
ELE07-00544 Electrical Rough-In2/22/20072/23/20072/22/2007 4:12:31 PMPCANC
jerry; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Patricia Smith