BLD05-03054
| FIRE-Final Inspection | 2/23/2007 | 2/23/2007 | 2/23/2007 4:18:25 PM | P | CANC |
|
|
Wrong job called in. No inspection performed.
|
BLD05-02719
| FIRE-Final Inspection | 2/23/2007 | 2/23/2007 | 2/23/2007 4:17:10 PM | P | FAIL |
|
|
No smoke barrier/draft curtain has been installed per the review comments and details on drawing sheets A4 to A6. All other life safety items ok.
|
FIR06-00499
| INSP-Final Inspection | 2/23/2007 | 2/23/2007 | 2/23/2007 4:15:30 PM | P | PASS |
|
|
Permit finaled
|
BLD05-01452
| FIRE-Final Inspection | 2/22/2007 | 2/23/2007 | 2/23/2007 3:27:02 PM | A | FAIL |
|
|
Need to test the smoke detectors that operate the fire/smoke doors and perform a complete inspection. Per Dan Stuart the occupancy will only be for the remodeled area. The remaining tenant area appears to be operating without an occupancy permit. I informed Mark in the fire department and he stated that he would follow up.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 2/22/2007 | 2/23/2007 | 2/23/2007 3:22:55 PM | A | PASS |
|
|
9th floor sprinkler rough-in passed.
|
FIR07-00094
| INSP-Sprinkler Rough-in/Hydro | 2/23/2007 | 2/23/2007 | 2/23/2007 11:34:23 AM | A | PASS |
|
|
Sprinkler rough-in is passed. Insulation at the roof deck is falling on the piping/uprights and will need to be attached to the roof structur prior to a cover inspection being passed.
|
FIR07-00099
| INSP-Sprinkler Rough-in | 2/22/2007 | 2/23/2007 | 2/23/2007 10:24:47 AM | A | PASS |
|
|
Sprinkler piping is ok to cover.
|
FIR06-00600
| INSP-Final Inspection | 2/22/2007 | 2/23/2007 | 2/23/2007 9:01:46 AM | A | PASS |
|
|
permit finaled
|