Inspections for the day of: Monday, February 23, 2009.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00135 INSP-Sprinkler Rough-in/Hydro2/23/20092/23/20092/23/2009 5:12:38 PMPPASS
Ok to cover two sprinklers in a soffit area.
FIR08-00855 INSP-Sprinkler Rough-in2/23/20092/23/20092/23/2009 5:11:37 PMPFAIL
Resubmittal of drawings required. Drawings do not match installation. Antifreeze system was installed instead of the dry system that was shown on the plans.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro2/23/20092/23/20092/23/2009 5:10:04 PMPPASS
Ok to cover the corridors on the 9th and 11th Floor
FIR08-00045 INSP-Sprinkler Rough-in/Hydro2/23/20092/23/20092/23/2009 5:09:01 PMPPASS
Hydro Test Passed for wet and AnitFreeze
BLD07-02290 FIRE-Final Inspection2/23/20092/23/20092/23/2009 4:09:03 PMPFAIL
Provide self closing exit doors to the common exit doors and provide the apartment numbers.
BLD09-00152 FIRE-Final Inspection2/20/20092/23/20092/23/2009 3:00:52 PMAPASS
life safety passed
FIR07-01042 INSP-Final Inspection2/23/20092/23/20092/23/2009 2:50:44 PMPPASS
Permit finaled
FIR07-00928 INSP-Final Inspection2/23/20092/23/20092/23/2009 2:47:51 PMPPASS
Permit finaled
BLD06-01451 FIRE-Final Inspection2/20/20092/23/20092/23/2009 2:46:34 PMAFAIL
All life safety items except the exit signs, emergency lights and exit discharge lights appear to be ok. The exit signs, emergency lights and exit discharge lights will be tested tomorrow. The project related fire alarm permit still has two issues that need to be addressed prior to a final occupancy.
BLD09-00161 FIRE-Final Inspection2/23/20092/23/20092/23/2009 12:09:28 PMPPASS
life safety passed
FIR08-00778 INSP-Sprinkler Rough-in/Hydro2/23/20092/23/20092/23/2009 11:58:07 AMAFAIL
The insulation had not been addressed on the second floor mezzanine so the inspection was stopped until all items are addressed. Per the contractor other areas will be ready at the next inspection.
BLD09-00185 FIRE-Final Inspection2/20/20092/23/20092/23/2009 11:56:44 AMAPART
A temporary occupancy was given until the fire extinguisher is provided as discussed, the exit signs/emergency lights are provided and the electrical floor recepticles are covered.
FIR08-00045 INSP-Sprinkler Rough-in/Hydro2/20/20092/23/20092/23/2009 10:22:17 AMAFAIL
Hydro test was not even started due to the fitter finding a leak.